18.7.10
Function commands for IEC 60870-5-103 I103CMD
18.7.10.1
Functionality
I103CMD is a command function block in control direction with pre-defined output
signals. The signals are in steady state, not pulsed, and stored in the IED in case of restart.
18.7.10.2
Identification
Function description
Function block
name
IEC 60617
identification
ANSI/IEEE C37.2
device number
Function commands for IEC
60870-5-103
I103CMD
-
-
18.7.10.3
Function block
IEC10000282-1-en.vsd
I103CMD
BLOCK
16-AR
17-DIFF
18-PROT
IEC10000282 V1 EN
Figure 251:
I103CMD function block
18.7.10.4
Signals
Table 523:
I103CMD Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of commands
Table 524:
I103CMD Output signals
Name
Type
Description
16-AR
BOOLEAN
Information number 16 disable/enable autorecloser
17-DIFF
BOOLEAN
Information number 17, block of differential protection
18-PROT
BOOLEAN
Information number 18, block of protection
18.7.10.5
Settings
Table 525:
I103CMD Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
1
Function type (1-255)
1MRK 511 365-UUS A
Section 18
Station communication
Phasor measurement unit RES670 2.1 ANSI
655
Technical manual
Summary of Contents for Relion 670 Series RES670
Page 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 76: ...70 ...
Page 106: ...100 ...
Page 150: ...144 ...
Page 274: ...268 ...
Page 326: ...320 ...
Page 356: ...350 ...
Page 382: ...376 ...
Page 416: ...410 ...
Page 590: ...584 ...
Page 604: ...598 ...
Page 694: ...688 ...
Page 756: ...750 ...
Page 834: ...828 ...
Page 836: ...830 ...
Page 876: ...870 ...
Page 886: ...880 ...
Page 887: ...881 ...