Name
Values (Range)
Unit
Step
Default
Description
DirModeSel2
Disabled
Non-directional
Forward
Reverse
-
-
Non-directional
Directional mode of step 2 (Disabled, Nondir,
Forward, Reverse)
Characterist2
ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
-
-
ANSI Def. Time
Time delay characteristic for step 2
I2-2>
1 - 2500
%IB
1
50
Negative sequence current op level for step 2
in % of IBase
t2
0.000 - 60.000
s
0.001
0.400
Time delay of step 2 when definite time char. is
selected
TD2
0.05 - 999.00
-
0.01
0.05
Time multiplier for the step 2 selected time
characteristic
IMin2
1.00 - 10000.00
%IB
1.00
50
Minimum current for step 2
t2Min
0.000 - 60.000
s
0.001
0.000
Minimum operate time for inverse time
characteristic step 2
MultPU2
1.0 - 10.0
-
0.1
2.0
Multiplier for scaling the current setting value
for step 2
DirModeSel3
Disabled
Non-directional
Forward
Reverse
-
-
Non-directional
Directional mode of step 3 (Disabled, Nondir,
Forward, Reverse)
Table continues on next page
Section 8
1MRK 511 365-UUS A
Current protection
216
Phasor measurement unit RES670 2.1 ANSI
Technical manual
Summary of Contents for Relion 670 Series RES670
Page 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 76: ...70 ...
Page 106: ...100 ...
Page 150: ...144 ...
Page 274: ...268 ...
Page 326: ...320 ...
Page 356: ...350 ...
Page 382: ...376 ...
Page 416: ...410 ...
Page 590: ...584 ...
Page 604: ...598 ...
Page 694: ...688 ...
Page 756: ...750 ...
Page 834: ...828 ...
Page 836: ...830 ...
Page 876: ...870 ...
Page 886: ...880 ...
Page 887: ...881 ...