Table 16:
TRM_6I Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
CT_WyePoint1
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec1
1 - 10
A
1
1
Rated CT secondary current
CTprim1
1 - 99999
A
1
3000
Rated CT primary current
CT_WyePoint2
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec2
1 - 10
A
1
1
Rated CT secondary current
CTprim2
1 - 99999
A
1
3000
Rated CT primary current
CT_WyePoint3
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec3
1 - 10
A
1
1
Rated CT secondary current
CTprim3
1 - 99999
A
1
3000
Rated CT primary current
CT_WyePoint4
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec4
1 - 10
A
1
1
Rated CT secondary current
CTprim4
1 - 99999
A
1
3000
Rated CT primary current
CT_WyePoint5
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec5
1 - 10
A
1
1
Rated CT secondary current
CTprim5
1 - 99999
A
1
3000
Rated CT primary current
CT_WyePoint6
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec6
1 - 10
A
1
1
Rated CT secondary current
CTprim6
1 - 99999
A
1
3000
Rated CT primary current
Table 17:
TRM_7I_5U Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
CT_WyePoint1
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec1
1 - 10
A
1
1
Rated CT secondary current
CTprim1
1 - 99999
A
1
3000
Rated CT primary current
CT_WyePoint2
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec2
1 - 10
A
1
1
Rated CT secondary current
CTprim2
1 - 99999
A
1
3000
Rated CT primary current
CT_WyePoint3
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec3
1 - 10
A
1
1
Rated CT secondary current
Table continues on next page
Section 3
1MRK 511 365-UUS A
Analog inputs
62
Phasor measurement unit RES670 2.1 ANSI
Technical manual
Summary of Contents for Relion 670 Series RES670
Page 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 76: ...70 ...
Page 106: ...100 ...
Page 150: ...144 ...
Page 274: ...268 ...
Page 326: ...320 ...
Page 356: ...350 ...
Page 382: ...376 ...
Page 416: ...410 ...
Page 590: ...584 ...
Page 604: ...598 ...
Page 694: ...688 ...
Page 756: ...750 ...
Page 834: ...828 ...
Page 836: ...830 ...
Page 876: ...870 ...
Page 886: ...880 ...
Page 887: ...881 ...