NoEvents
•
OnSet
•
OnReset
•
OnChange
•
AutoDetect
It is possible to define which part of EVENT function generates the events. This can be
performed individually for the
SPAChannelMask
and
LONChannelMask
respectively.
For each communication type these settings are available:
•
Disabled
•
Channel 1-8
•
Channel 9-16
•
Channel 1-16
For LON communication the events normally are sent to station level at change. It is
possibly also to set a time for cyclic sending of the events individually for each input
channel.
To protect the SA system from signals with a high change rate that can easily saturate the
event system or the communication subsystems behind it, a quota limiter is implemented.
If an input creates events at a rate that completely consume the granted quota then further
events from the channel will be blocked. This block will be removed when the input calms
down and the accumulated quota reach 66% of the maximum burst quota. The maximum
burst quota per input channel is 45 events per second.
16.6
Disturbance report DRPRDRE
16.6.1
Identification
Function description
IEC 61850 identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Disturbance report
DRPRDRE
-
-
Disturbance report
A1RADR - A4RADR
-
-
Disturbance report
B1RBDR - B8RBDR
-
-
Section 16
1MRK 511 365-UUS A
Monitoring
544
Phasor measurement unit RES670 2.1 ANSI
Technical manual
Summary of Contents for Relion 670 Series RES670
Page 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 76: ...70 ...
Page 106: ...100 ...
Page 150: ...144 ...
Page 274: ...268 ...
Page 326: ...320 ...
Page 356: ...350 ...
Page 382: ...376 ...
Page 416: ...410 ...
Page 590: ...584 ...
Page 604: ...598 ...
Page 694: ...688 ...
Page 756: ...750 ...
Page 834: ...828 ...
Page 836: ...830 ...
Page 876: ...870 ...
Page 886: ...880 ...
Page 887: ...881 ...