17.1.4
Signals
Table 455:
PCFCNT Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
READ_VAL
BOOLEAN
0
Initiates an additional pulse counter reading
BI_PULSE
BOOLEAN
0
Connect binary input channel for metering
RS_CNT
BOOLEAN
0
Resets pulse counter value
Table 456:
PCFCNT Output signals
Name
Type
Description
INVALID
BOOLEAN
The pulse counter value is invalid
RESTART
BOOLEAN
The reported value does not comprise a complete
integration cycle
BLOCKED
BOOLEAN
The pulse counter function is blocked
NEW_VAL
BOOLEAN
A new pulse counter value is generated
SCAL_VAL
REAL
Scaled value with time and status information
17.1.5
Settings
Table 457:
PCFCNT Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Disabled/Enabled
EventMask
NoEvents
ReportEvents
-
-
NoEvents
Report mask for analog events from pulse
counter
CountCriteria
Disabled
RisingEdge
Falling edge
OnChange
-
-
RisingEdge
Pulse counter criteria
Scale
1.000 - 90000.000
-
0.001
1.000
Scaling value for SCAL_VAL output to unit per
counted value
Quantity
Count
ActivePower
ApparentPower
ReactivePower
ActiveEnergy
ApparentEnergy
ReactiveEnergy
-
-
Count
Measured quantity for SCAL_VAL output
tReporting
0 - 3600
s
1
60
Cycle time for reporting of counter value
Section 17
1MRK 511 365-UUS A
Metering
586
Phasor measurement unit RES670 2.1 ANSI
Technical manual
Summary of Contents for Relion 670 Series RES670
Page 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 76: ...70 ...
Page 106: ...100 ...
Page 150: ...144 ...
Page 274: ...268 ...
Page 326: ...320 ...
Page 356: ...350 ...
Page 382: ...376 ...
Page 416: ...410 ...
Page 590: ...584 ...
Page 604: ...598 ...
Page 694: ...688 ...
Page 756: ...750 ...
Page 834: ...828 ...
Page 836: ...830 ...
Page 876: ...870 ...
Page 886: ...880 ...
Page 887: ...881 ...