a
b
b>a
Selected current
PickupCurr_UC1
Operation_UC1=On
Bin input: BLKUC1
PU_UC1
en05000750_ansi.vsd
TRUC1
Bin input: BLKUC1TR
0-DEF
AND
AND
0
ANSI05000750 V1 EN
Figure 119:
Simplified internal logic diagram for built-in first undercurrent step that is, UC1 (step UC2 has the same
internal logic)
a
b
a>b
Selected voltage
PickupVolt_OV1
Operation_OV1=On
BLKOV1
Inverse time
selected
en05000751_ansi.vsd
Inverse
0-DEF
DEF time
selected
PU_OV1
TROV1
AND
BLKTROV1
AND
OR
0
ANSI05000751 V1 EN
Figure 120:
Simplified internal logic diagram for built-in first overvoltage step OV1 (step OV2 has the same internal
logic)
Section 11
1MRK 511 365-UUS A
Multipurpose protection
346
Phasor measurement unit RES670 2.1 ANSI
Technical manual