Each analog output has a corresponding supervision level output (X_RANGE). The
output signal is an integer in the interval 0-4, see section
Calibration of analog inputs
Measured currents and voltages used in the CVMMXN function can be calibrated to get
class 0.5 measuring accuracy. This is achieved by magnitude and angle compensation at
5, 30 and 100% of rated current and voltage. The compensation below 5% and above
100% is constant and linear in between, see example in figure
.
100
30
5
IMagComp5
IMagComp30
IMagComp100
-10
+10
Magnitude
compensation
% of In
Measured
current
% of In
0-5%:
Constant
5-30-100%: Linear
>100%:
Constant
100
30
5
IAngComp5
IAngComp30
IAngComp100
-10
+10
Angle
compensation
Degrees
Measured
current
% of In
ANSI05000652_3_en.vsd
ANSI05000652 V3 EN
Figure 191:
Calibration curves
The first current and voltage phase in the group signals will be used as reference and the
magnitude and angle compensation will be used for related input signals.
Low pass filtering
In order to minimize the influence of the noise signal on the measurement it is possible to
introduce the recursive, low pass filtering of the measured values for P, Q, S, V, I and
power factor. This will make slower measurement response to the step changes in the
1MRK 511 365-UUS A
Section 16
Monitoring
Phasor measurement unit RES670 2.1 ANSI
513
Technical manual
Summary of Contents for Relion 670 Series RES670
Page 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 76: ...70 ...
Page 106: ...100 ...
Page 150: ...144 ...
Page 274: ...268 ...
Page 326: ...320 ...
Page 356: ...350 ...
Page 382: ...376 ...
Page 416: ...410 ...
Page 590: ...584 ...
Page 604: ...598 ...
Page 694: ...688 ...
Page 756: ...750 ...
Page 834: ...828 ...
Page 836: ...830 ...
Page 876: ...870 ...
Page 886: ...880 ...
Page 887: ...881 ...