10.2.2
Functionality
Overfrequency protection function SAPTOF (81) is applicable in all situations, where
reliable detection of high fundamental power system frequency is needed.
Overfrequency occurs because of sudden load drops or shunt faults in the power network.
Close to the generating plant, generator governor problems can also cause over frequency.
SAPTOF (81) measures frequency with high accuracy, and is used mainly for generation
shedding and remedial action schemes. It is also used as a frequency stage initiating load
restoring. A definite time delay is provided for trip.
SAPTOF (81) is provided with an undervoltage blocking.
The operation is based on positive sequence voltage measurement and requires two phase-
phase or three phase-neutral voltages to be connected. For information about how to
connect analog inputs, refer to
Application manual/IED application/Analog inputs/
Setting guidelines
10.2.3
Function block
ANSI06000280-2-en.vsd
SAPTOF (81)
V3P*
BLOCK
BLKTRIP
TRIP
PICKUP
BLKDMAGN
FREQ
ANSI06000280 V2 EN
Figure 104:
SAPTOF (81) function block
10.2.4
Signals
Table 168:
SAPTOF (81H) Input signals
Name
Type
Default
Description
V3P
GROUP
SIGNAL
-
Three phase group signal for voltage inputs
BLOCK
BOOLEAN
0
Block of function
BLKTRIP
BOOLEAN
0
Blocking operate output
Section 10
1MRK 511 365-UUS A
Frequency protection
304
Phasor measurement unit RES670 2.1 ANSI
Technical manual
Summary of Contents for Relion 670 Series RES670
Page 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 76: ...70 ...
Page 106: ...100 ...
Page 150: ...144 ...
Page 274: ...268 ...
Page 326: ...320 ...
Page 356: ...350 ...
Page 382: ...376 ...
Page 416: ...410 ...
Page 590: ...584 ...
Page 604: ...598 ...
Page 694: ...688 ...
Page 756: ...750 ...
Page 834: ...828 ...
Page 836: ...830 ...
Page 876: ...870 ...
Page 886: ...880 ...
Page 887: ...881 ...