20.9.3
Signals
Table 604:
TESTMODE Input signals
Name
Type
Default
Description
IED_TEST
BOOLEAN
0
Activate IED test mode
Table 605:
TESTMODE Output signals
Name
Type
Description
TEST
BOOLEAN
In test via IED TEST or via LD0 Mode
IED_TEST
BOOLEAN
IED test mode is active
BLOCK
BOOLEAN
Active when LD0 is blocked or test blocked
NOEVENT
BOOLEAN
Event disabled during test mode
INPUT
BOOLEAN
IED TEST input is active
SETTING
BOOLEAN
IED test mode setting is On
IEC61850
BOOLEAN
Active when LD0 Mode is in Blocked, Test or Test
blocked
20.9.4
Settings
Table 606:
TESTMODE Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
IEDTestMode
Disabled
Enabled
-
-
Disabled
Activate IED Test mode
EventDisable
Disabled
Enabled
-
-
Disabled
Event disable during test mode
BlockAllFunc
Disabled
Enabled
-
-
Enabled
Block all functions when entering IED test
mode
CmdTestEd1
Disabled
Enabled
-
-
Disabled
Require test bit in command at test mode (only
for IEC61850 Ed1)
20.9.5
Operation principle
Set the IED in test mode by
•
configuration, activating the input SIGNAL on the function block TESTMODE.
•
setting
TestMode
to
Enabled
in the local HMI, under
Main menu/TEST/IED test
mode
.
1MRK 511 365-UUS A
Section 20
Basic IED functions
Phasor measurement unit RES670 2.1 ANSI
729
Technical manual
Summary of Contents for Relion 670 Series RES670
Page 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 76: ...70 ...
Page 106: ...100 ...
Page 150: ...144 ...
Page 274: ...268 ...
Page 326: ...320 ...
Page 356: ...350 ...
Page 382: ...376 ...
Page 416: ...410 ...
Page 590: ...584 ...
Page 604: ...598 ...
Page 694: ...688 ...
Page 756: ...750 ...
Page 834: ...828 ...
Page 836: ...830 ...
Page 876: ...870 ...
Page 886: ...880 ...
Page 887: ...881 ...