13.2.6
Monitored data
Table 211:
FUFSPVC Monitored data
Name
Type
Values (Range)
Unit
Description
3I0
REAL
-
A
Magnitude of zero sequence
current
3I2
REAL
-
A
Magnitude of negative
sequence current
3V0
REAL
-
kV
Magnitude of zero sequence
voltage
3V2
REAL
-
kV
Magnitude of negative
sequence voltage
13.2.7
Operation principle
13.2.7.1
Zero and negative sequence detection
The zero and negative sequence function continuously measures the currents and voltages
in all three phases and calculates, see figure
•
the zero-sequence voltage 3V0
•
the zero-sequence current 3I0
•
the negative sequence current 3I2
•
the negative sequence voltage 3V2
The measured signals are compared with their respective set values
3V0PU
and
3I0PU
,
3V2PU
and
3I2PU
.
The function enable the internal signal FuseFailDetZeroSeq if the measured zero-
sequence voltage is higher than the set value
3V0PU
and the measured zero-sequence
current is below the set value
3I0PU
.
The function enable the internal signal FuseFailDetNegSeq if the measured negative
sequence voltage is higher than the set value
3V2PU
and the measured negative sequence
current is below the set value
3I2PU
.
A drop out delay of 100 ms for the measured zero-sequence and negative sequence current
will prevent a false fuse failure detection at un-equal breaker opening at the two line ends.
Section 13
1MRK 511 365-UUS A
Secondary system supervision
366
Phasor measurement unit RES670 2.1 ANSI
Technical manual
Summary of Contents for Relion 670 Series RES670
Page 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 76: ...70 ...
Page 106: ...100 ...
Page 150: ...144 ...
Page 274: ...268 ...
Page 326: ...320 ...
Page 356: ...350 ...
Page 382: ...376 ...
Page 416: ...410 ...
Page 590: ...584 ...
Page 604: ...598 ...
Page 694: ...688 ...
Page 756: ...750 ...
Page 834: ...828 ...
Page 836: ...830 ...
Page 876: ...870 ...
Page 886: ...880 ...
Page 887: ...881 ...