What to do
Cause
Event name /
Aux. code
Code
(hex)
above). “ZZ” indicates the phase (1: U,
2: V, 3: W).
Check there are no power factor
correction capacitors or surge
absorbers in motor cable.
Total earth leakage of inverter
modules is excessive.
BU earth
leakage
2392
Measure insulation resistances of
motor cables and motor.
Contact your local ABB representative.
Check AC fuses.
IGBT supply unit has detected an earth
fault.
Earth leakage
2E01
Check for earth leakages.
Check supply cabling.
Check power modules.
Check there are no power factor
correction capacitors or surge
absorbers in supply cable.
If no earth fault can be detected,
contact your local ABB representative.
Check that the speed points of the
curve (defined by
29.70 Speed data
Parametrization of the speed/torque
limitation curve (in the DC voltage
reference chain) are inconsistent.
Invalid
voltage chain
datapoints
3000
point 1…29.79 Torque data point 5)
are in increasing order.
Check input power line fuses.
Intermediate circuit DC voltage is
oscillating due to missing input power
line phase or blown fuse.
Supply phase
loss
3130
Check for loose power cable
connections.
Check for input power supply
imbalance.
Contact your local ABB representative.
No acknowledgement received from
charge relay.
Charge relay
lost
3180
Wiring or
earth fault
3181
1.
Switch off the protection in
parameter
.
1.
The drive hardware is supplied
from a common DC bus.
2.
Incorrect input power and motor
cable connection (i.e. input power
2.
Check the power connections.
Check the input fuses.
cable is connected to the motor
connection).
3.
Check there are no power factor
correction capacitors or surge
absorbers in motor cable.
3.
Drive has detected load
unbalance typically due to earth
fault in motor or motor cable.
Check for an earth fault in motor
or motor cables by measuring the
insulation resistances of motor
and motor cable.
Try running the motor in scalar
control mode if allowed. (See
parameter
99.4 Motor control
mode.)
Check that overvoltage control is on
(parameter
).
Excessive intermediate circuit DC
voltage.
DC link
overvoltage
3210
Check that the supply voltage matches
the nominal input voltage of the drive.
Check the supply line for static or
transient overvoltage.
Fault tracing 655
Summary of Contents for ACS880 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Page 2: ......
Page 4: ......
Page 16: ...16 ...
Page 22: ...22 ...
Page 24: ...24 ...
Page 44: ...44 ...
Page 66: ...66 ...
Page 148: ...148 ...
Page 168: ...168 ...
Page 704: ...704 ...
Page 728: ...728 ...
Page 742: ...742 ...
Page 762: ...762 ...