Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
10 = 1 / 100 = 1
Overload curve point 3.
-30000.00 ...
30000.00
0.00 / real32
Defines overload curve point 4 load limit active at
corresponding speed set in parameter
.
Overload curve point
4
79.54
10 = 1 / 100 = 1
Overload curve point 4.
-30000.00 ...
30000.00
0.00 / real32
Defines overload curve point 5 load limit active at
corresponding speed set in parameter
.
Overload curve point
5
79.55
10 = 1 / 100 = 1
Overload curve point 5.
-30000.00 ...
30000.00
1.000 / real32
Defines multiplier coefficient applied to the overload
limit calculated out of the overload curve.
Overload curve scale
coef
79.58
100 = 1 / 1000 = 1
Overload curve scale coef.
-30.000 ... 30.000
0.00 / real32
Defines offset additive value applied to the overload
limit calculated out of the overload curve.
Overload curve
offset
79.59
10 = 1 / 100 = 1
Overload curve offset.
-30000.00 ...
30000.00
10.00 Hz / real32
Defines speed reference used in course of the overload
recovery routine.
Overload recovery
speed
79.61
10 = 1 Hz / 100 = 1 Hz
Overload safe speed.
0.00 ... 598.00 Hz
60.0 s / real32
Defines time for the overload recovery routine to stay
active.
Overload recovery
speed time
79.62
1 = 1 s / 10 = 1 s
Overload safe speed time.
0.0 ... 30000.0 s
0.00 / real32
Displays currently active underload limit.
Underload actual
limit
79.80
10 = 1 / 100 = 1
Underload actual limit.
-30000.00 ...
30000.00
0.0 s / real32
Displays the delay time remaining before underload
condition response is triggered.
Underload trip count
down
79.81
10 = 1 s / 10 = 1 s
Underload actual limit.
0.0 ... 30000.0 s
- / real32
Displays the number of underload recovery attempts
made.
URT recovery
attempts
79.89
1 = 1 / -
URT recovery attempts.
0...100
0.00 / real32
Displays currently active overload limit.
Overload actual limit
79.90
10 = 1 / -
Overload actual limit.
-30000.00 ...
30000.00
0.0 s / real32
Displays the delay time remaining before overload
condition response is triggered.
Overload trip count
down
79.91
10 = 1 s / 10 = 1 s
Overload trip count down.
0.0 ... 30000.0 s
- / unit16
Displays the status word for the load protection
function.
Load protection
status word
79.99
544 Parameters
Summary of Contents for ACS880 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Page 2: ......
Page 4: ......
Page 16: ...16 ...
Page 22: ...22 ...
Page 24: ...24 ...
Page 44: ...44 ...
Page 66: ...66 ...
Page 148: ...148 ...
Page 168: ...168 ...
Page 704: ...704 ...
Page 728: ...728 ...
Page 742: ...742 ...
Page 762: ...762 ...