![ABB ACS880 Series Firmware Manual Download Page 283](http://html.mh-extra.com/html/abb/acs880-series/acs880-series_firmware-manual_2617283.webp)
Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
4
The sources of the start and stop commands are
selected by parameters
and
The state transitions of the source bits are interpreted
as follows:
Command
State of source 2
State of source 1
(
)
Start
1
0?1
Stop
0
Any
Note: The start signal is always edge-triggered with
this setting regardless of parameter
.
In1P Start; In2 Stop
5
The sources of the start and stop commands are
selected by parameters
and
The source selected by
determines the direction. The state transitions of the
source bits are interpreted as follows:
Command
State of
source 3
(
)
State of
source 2
State of
source 1
(
)
Start forward
0
1
0?1
Start reverse
1
1
0?1
Stop
Any
0
Any
Note: The start signal is always edge-triggered with
this setting regardless of parameter
.
In1P Start; In2 Stop;
In3 Dir
6
The sources of the start and stop commands are
selected by parameters
,
and
. The state
transitions of the source bits are interpreted as follows:
Command
State of
source 3
(
)
State of
source 2
State of
source 1
(
)
Start forward
1
Any
0?1
Start reverse
1
0?1
Any
Stop
0
Any
Any
Note: The start signal is always edge-triggered with
this setting regardless of parameter
.
In1P Start fwd; In2P
Start rev; In3 Stop
11
The start and stop commands are taken from the
control panel.
Control panel
Parameters 283
Summary of Contents for ACS880 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Page 2: ......
Page 4: ......
Page 16: ...16 ...
Page 22: ...22 ...
Page 24: ...24 ...
Page 44: ...44 ...
Page 66: ...66 ...
Page 148: ...148 ...
Page 168: ...168 ...
Page 704: ...704 ...
Page 728: ...728 ...
Page 742: ...742 ...
Page 762: ...762 ...