![ABB ACS880 Series Firmware Manual Download Page 280](http://html.mh-extra.com/html/abb/acs880-series/acs880-series_firmware-manual_2617280.webp)
Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
4
The sources of the start and stop commands are
selected by parameters
and
.
The state transitions of the source bits are interpreted
as follows:
Command
State of source 2
)
State of source 1
)
Start
1
0?1
Stop
0
Any
Note: The start signal is always edge-triggered with
this setting regardless of parameter
.
In1P Start; In2 Stop
5
The sources of the start and stop commands are
selected by parameters
and
.
The source selected by
determines
the direction. The state transitions of the source bits
are interpreted as follows:
Command
State of
source 3
(
)
State of
source 2
)
State of
source 1
)
Start forward
0
1
0?1
Start reverse
1
1
0?1
Stop
Any
0
Any
Note: The start signal is always edge-triggered with
this setting regardless of parameter
.
In1P Start; In2 Stop;
In3 Dir
6
The sources of the start and stop commands are
selected by parameters
and
. The state
transitions of the source bits are interpreted as follows:
Command
State of
source 3
(
)
State of
source 2
)
State of
source 1
)
Start forward
1
Any
0?1
Start reverse
1
0?1
Any
Stop
0
Any
Any
Note: The start signal is always edge-triggered with
this setting regardless of parameter
.
In1P Start fwd; In2P
Start rev; In3 Stop
11
The start and stop commands are taken from the
control panel.
Control panel
280 Parameters
Summary of Contents for ACS880 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Page 2: ......
Page 4: ......
Page 16: ...16 ...
Page 22: ...22 ...
Page 24: ...24 ...
Page 44: ...44 ...
Page 66: ...66 ...
Page 148: ...148 ...
Page 168: ...168 ...
Page 704: ...704 ...
Page 728: ...728 ...
Page 742: ...742 ...
Page 762: ...762 ...