Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
Configuration of maintenance timers/counters.
Generic timer &
counter
33
See also section
.
- / uint16
Displays the maintenance timer/counter status word,
indicating which maintenance timers/counters have
exceeded their limits.
Counter status
33.1
This parameter is read-only.
1 = On-time timer 1 has reached its preset limit.
On-time 1
b0
1 = On-time timer 2 has reached its preset limit.
On-time 2
b1
1 = Signal edge counter 1 has reached its preset limit.
Edge 1
b2
1 = Signal edge counter 2 has reached its preset limit.
Edge 2
b3
1 = Value counter 1 has reached its preset limit.
Value 1
b4
1 = Value counter 2 has reached its preset limit.
Value 2
b5
Reserved
b6…15
1 = 1
0000h…FFFFh
- / uint32
Displays the actual present value of on-time timer 1.
The timer runs whenever the signal selected by
parameter
is on.
On-time 1 actual
33.10
When the timer exceeds the limit set by
, bit 0 of
is set to 1. The
warning specified by
is
also given if enabled by
The timer can be reset from the Drive Composer PC
tool, or from the control panel by keeping Reset
depressed for over 3 seconds.
- / -
Actual present value of on-time timer 1.
0...4294967295 s
- / uint32
Sets the warning limit for on-time timer 1.
On-time 1 warn limit
33.11
- / -
Warning limit for on-time timer 1.
0...4294967295 s
- / uint16
Configures on-time timer 1.
On-time 1 function
33.12
0 = Loop: When the limit is reached, the counter is reset.
The counter status (bit 0 of
) switches to 1 for one
Counter mode
b0
second. The warning (if enabled) stays active for at
least 10 seconds.
1 = Saturate: When the limit is reached, the counter
status (bit 0 of
) switches to 1, and remains so until
is reset. The warning (if enabled) also stays active
until
is reset.
0 = Disable: No warning is given when the limit is
reached
Warning enable
b1
1 = Enable: A warning (see
) is given when the limit
is reached
Reserved
b2…15
1 = 1
0000h…FFFFh
False / uint32
Selects the signal to be monitored by on-time timer 1.
On-time 1 source
33.13
0
Constant 0 (timer disabled).
False
Parameters 389
Summary of Contents for ACS880 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Page 2: ......
Page 4: ......
Page 16: ...16 ...
Page 22: ...22 ...
Page 24: ...24 ...
Page 44: ...44 ...
Page 66: ...66 ...
Page 148: ...148 ...
Page 168: ...168 ...
Page 704: ...704 ...
Page 728: ...728 ...
Page 742: ...742 ...
Page 762: ...762 ...