![ABB ACS880 Series Firmware Manual Download Page 527](http://html.mh-extra.com/html/abb/acs880-series/acs880-series_firmware-manual_2617527.webp)
Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
0 / real32
Defines custom scaling for the parameter
Ext2 speed ref scaler
75.17
1 = 1 / 1 = 1
Speed reference scalar.
0...30000
0.00 Hz / real32
Defines minimum production speed reference in
absolute value.
Minimum
production speed
75.18
10 = 1 Hz / 100 = 1 Hz
Minimum production speed.
0.00 ... 598.00 Hz
50.00 Hz / real32
Defines maximum production speed reference in
absolute value.
Maximum
production speed
75.19
10 = 1 Hz / 100 = 1 Hz
Maximum production speed.
0.00 ... 598.00 Hz
30.0 s / real32
Defines the time for the pump-motor to accelerate
from 0 up to the speed set in parameter
Note: If parameter
is set to
greater than 0, then this parameter ramp time setting
is used while speed reference is in lower speed region.
Acceleration time
75.21
1 = 1 s / 10 = 1 s
Acceleration time in seconds.
0.0 ... 1800.0 s
30.0 s / real32
Defines the time for the pump-motor to decelerate
from the speed set in parameter
down to 0.
Note: If parameter
is set to
greater than 0, then this parameter ramp time setting
is used while speed reference is in lower speed region.
Deceleration time
75.22
1 = 1 s / 10 = 1 s
Deceleration time in seconds.
0.0 ... 1800.0 s
0.00 Hz / real32
Defines the speed at which ramp time should switch
from ramp set 1 to ramp set 2.
•
Ramp set 1 (
and
) is used in speed range from
up to
•
When speed reference gets higher than
and
•
If parameter value is "0", then only ramp set 1 is
used for the complete production speed range.
Ramp switch speed
75.23
10 = 1 Hz / 100 = 1 Hz
Ramp switch speed.
0.00 ... 598.00 Hz
30.0 s / real32
Defines the time for the pump-motor to accelerate
from 0 up to the speed set in parameter
Note: If parameter
is set to
greater than 0, then this parameter ramp time setting
is used while speed reference is in lower speed region.
Acceleration time 2
75.24
1 = 1 s / 10 = 1 s
Acceleration time 2 in seconds.
0.0 ... 1800.0 s
Parameters 527
Summary of Contents for ACS880 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...