Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
- / uint16
Activates/deactivates the DC hold and
post-magnetization functions. See section
.
Note:
•
DC hold is only available with speed control in DTC
motor control mode (see page
•
DC magnetization causes the motor to heat up.
In applications where long DC magnetization
times are required, externally ventilated motors
should be used. If the DC magnetization period is
long, DC magnetization cannot prevent the motor
shaft from rotating if a constant load is applied
to the motor.
DC current control
21.8
1 = Enable DC hold. See section
Note: The DC hold function has no effect if the start
signal is switched off.
DC hold
b0
1 = Enable post-magnetization. See section
Note: Post-magnetization is only available when
ramping is the selected stop mode (see parameter
Post magnetization
b1
Reserved
b2…15
1 = 1
0000h…FFFFh
5.00 rpm / real32
Defines the DC hold speed. See parameter
, and section
DC hold speed
21.9
- / -
DC hold speed. For scaling, see parameter
0.00 ... 1000.00 rpm
30.0 % / real32
Defines the DC hold current in percent of the motor
nominal current. See parameter
,
and section
DC current reference
21.10
1 = 1 % / 10 = 1 %
DC hold current.
0.0 ... 100.0 %
0 s / uint32
Defines the length of time for which
post-magnetization is active after stopping the motor.
The magnetization current is defined by parameter
See parameter
.
Post magnetization
time
21.11
1 = 1 s / 1 = 1 s
Post-magnetization time.
0...3000 s
Parameters 295
Summary of Contents for ACS880 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Page 2: ......
Page 4: ......
Page 16: ...16 ...
Page 22: ...22 ...
Page 24: ...24 ...
Page 44: ...44 ...
Page 66: ...66 ...
Page 148: ...148 ...
Page 168: ...168 ...
Page 704: ...704 ...
Page 728: ...728 ...
Page 742: ...742 ...
Page 762: ...762 ...