The scaled references are shown by parameters
and
■
Actual values
Actual values are 16-bit words containing information on the operation of the
drive. The types of the monitored signals are selected by parameters
and
.
Debugging the network words
If parameter
is set to
, the actual values sent to the
fieldbus are displayed by
and
Scaling of actual values
Note: The scalings described below are for the ABB Drives communication profile.
Fieldbus-specific communication profiles may use different scalings. For more
information, see the manual of the fieldbus adapter.
The actual values are scaled as defined by parameters
...
; which scaling
is in use depends on the setting of parameters
and
Fieldbus
Drive
20000
10000
0
-10000
-20000
46.01 (with speed reference)
46.02 (with frequency reference)
46.03 (with torque reference)
46.04 (with power reference)
-(46.03) (with torque reference)
-(46.04) (with power reference)
-(46.01) (with speed reference)
-(46.02) (with frequency reference)
0
734 Fieldbus control through a fieldbus adapter
Summary of Contents for ACS880 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Page 2: ......
Page 4: ......
Page 16: ...16 ...
Page 22: ...22 ...
Page 24: ...24 ...
Page 44: ...44 ...
Page 66: ...66 ...
Page 148: ...148 ...
Page 168: ...168 ...
Page 704: ...704 ...
Page 728: ...728 ...
Page 742: ...742 ...
Page 762: ...762 ...