Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
1 = 1 = 1
0000h…FFFFh
Drive not ready /
unit32
Displays the current state of drive control.
Drive control state
9.9
0
Drive is not ready for operation.
Drive not ready
1
No motor ID run done. Necessary to run in DTC mode.
ID run undone
2
Drive is stopped.
Drive stopped
3
A fault is active.
Fault active
4
Drive is in Local control.
Local control
5
Jogging enable signal is On.
Jog mode
6
Control location EXT1 is active.
Ext1 running
7
Control location EXT2 is active.
Ext2 running
8
Drive is stopping the motor as per deceleration ramp
time settings.
Stopping
9
Stopping after receiving an emergency stop command.
Em stop active
10
Drive is running in constant speed mode.
Constant speed
0.00 A / real32
Displays actual drive output current.
Drive output current
9.11
100 = 1 A / 100 = 1 A
Drive output current.
0.00 ... 30000.00 A
0.00 A / real32
Displays the actual motor current estimate based on
transformer ratio and sine-filter settings.
Motor current
estimated
9.13
100 = 1 A / 10 = 1 A
Estimated motor current.
0.00 ... 30000.00 A
0.00% / real32
Displays estimated actual motor current in %.
Motor current %
9.14
100 = 1% / 10 = 1%
Estimated motor current.
0.00 ... 30000.00%
0.00 V / real32
Displays the actual motor voltage estimate based on
transformer ratio setting.
Motor voltage
estimated
9.15
100 = 1 V / 10 V
Estimated motor voltage.
0.00 ... 30000.00 V
0.00 Hz / real32
Displays the frequency reference currently produced
by the ESP control program.
Frequency reference
used
9.21
100 = 1 Hz / 10 = 1 Hz
ESP frequency.
-600.00 ... 600.00 Hz
0.00% / real32
Displays ESP speed/frequency reference in percent
scale.
Speed reference
percentage
9.22
100 = 1% / 10 = 1%
Speed reference.
-1200.00 ...
1200.00%
0.00 rpm / real32
Displays the speed reference currently produced by the
ESP control program.
Speed reference
used
9.23
10 = 1 rpm / 10 = 1
rpm
Speed reference.
-30000.0 ... 30000.0
rpm
0.00 min / real32
Displays the time remaining before restart delay
function stops inhibiting the user start command.
Restart delay
remaining
9.41
10 = 1 min / 10 = 1
min
Restart delay time.
0.0 ... 30000.0 min
Parameters 209
Summary of Contents for ACS880 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Page 2: ......
Page 4: ......
Page 16: ...16 ...
Page 22: ...22 ...
Page 24: ...24 ...
Page 44: ...44 ...
Page 66: ...66 ...
Page 148: ...148 ...
Page 168: ...168 ...
Page 704: ...704 ...
Page 728: ...728 ...
Page 742: ...742 ...
Page 762: ...762 ...