What to do
Cause
Event name /
Aux. code
Code
(hex)
When converted into a 32-bit binary
number, the bits of the code indicate
the following:
31…28: Number of faulty inverter
module (0…11 decimal). 1111: STO_ACT
states of control unit and inverter
modules in conflict
27: STO_ACT state of inverter modules
26: STO_ACT state of control unit
25: STO1 of control unit
24: STO2 of control unit
23…12: STO1 of inverter modules 12…1
(Bits of non-existing modules set to
1)
11…0: STO2 of inverter modules 12…1
(Bits of non-existing modules set to
1)
Check safety circuit connections. For
more information, see appropriate
Safe torque off function is active, ie.
STO circuit 2 is broken.
Safe torque
off 2 loss
FA82
drive hardware manual and
description of parameter
indication run/stop (page 370)
.
Check the auxiliary code, The code
contains location information,
especially with parallel-connected
inverter modules.
When converted into a 32-bit binary
number, the bits of the code indicate
the following:
31…28: Number of faulty inverter
module (0…11 decimal). 1111: STO_ACT
states of control unit and inverter
modules in conflict
27: STO_ACT state of inverter modules
26: STO_ACT state of control unit
25: STO1 of control unit
24: STO2 of control unit
23…12: STO1 of inverter modules 12…1
(Bits of non-existing modules set to
1)
11…0: STO2 of inverter modules 12…1
(Bits of non-existing modules set to
1)
Contact your local ABB representative.
SW internal malfunction.
STO
diagnostics
failure
FA90
Memory unit
missing
FB11
•
Power down the control unit.
Check that the memory unit is
properly inserted into the control
unit.
•
No memory unit is attached to
the control unit.
•
The memory unit attached to the
control unit is empty.
•
Power down the control unit.
Attach a memory unit (with the
appropriate firmware) to the
control unit.
Fault tracing 693
Summary of Contents for ACS880 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Page 2: ......
Page 4: ......
Page 16: ...16 ...
Page 22: ...22 ...
Page 24: ...24 ...
Page 44: ...44 ...
Page 66: ...66 ...
Page 148: ...148 ...
Page 168: ...168 ...
Page 704: ...704 ...
Page 728: ...728 ...
Page 742: ...742 ...
Page 762: ...762 ...