What to do
Cause
Event name /
Aux. code
Code
(hex)
Check that encoder is not slipping.
Too much difference between
measured and estimated positions.
0003
Check parameter
several times
to verify that the autophasing
routine gives consistent results.
Check the motor model parameters.
Check that the zero pulses are given
correctly.
Rotor did not rotate as expected
between zero pulses.
0004
Check that the selected mode
(parameter
) is appropriate for
the motor.
Position estimate did not stabilize.
0005
Check that parameter
is not
changed to
during the
routine.
Measured position status
information changed.
0006
Contact your local ABB
representative.
General autophasing failure.
0007
Check that the selected mode
(parameter
) is supported by
the motor type.
Selected mode not supported.
0008
Contact your local ABB
representative.
(LV-Synchro) Standstill failure.
0009
Check the auxiliary code. Check the
source of the fault corresponding to
the code:
Input phase loss detected by the IGBT
bridge.
Input phase
loss
3E00
1: Phase A
2: Phase B
4: Phase C
8: Phase cannot be detected
Check the AC fuses.
Check for input power supply
imbalance.
Check the settings of parameters
and
Calculated motor cable temperature
has exceeded warning limit.
Motor cable
overload
4000
Check the dimensioning of the motor
cable in regard to required load.
Check ambient temperature. If it
exceeds 40 °C (104 °F), ensure that
Drive module temperature is
excessive.
Ambient
temperature
4100
load current does not exceed derated
load capacity of drive. See appropriate
Hardware manual.
Check drive module cooling air flow
and fan operation.
Check inside of cabinet and heatsink
of drive module for dust pick-up. Clean
whenever necessary.
Check proper cooling of the drive.
Control board temperature is too high.
Control board
temperature
4110
Check the auxiliary cooling fan.
Check ambient conditions.
Estimated drive IGBT temperature is
excessive.
IGBT
overtemperature
4210
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check motor power against drive
power.
Fault tracing 657
Summary of Contents for ACS880 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Page 2: ......
Page 4: ......
Page 16: ...16 ...
Page 22: ...22 ...
Page 24: ...24 ...
Page 44: ...44 ...
Page 66: ...66 ...
Page 148: ...148 ...
Page 168: ...168 ...
Page 704: ...704 ...
Page 728: ...728 ...
Page 742: ...742 ...
Page 762: ...762 ...