Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
10
Digital input/output DIO1 (
, bit
0).
DIO1
11
Digital input/output DIO2 (
, bit
1).
DIO2
See
Terms and abbreviations (page 169)
Other [bit]
0.0 / real32
Defines a deadband around the setpoint. Whenever
process feedback enters the deadband, a delay timer
starts. If the feedback remains within the deadband
longer than the delay (
), the
PID controller output is frozen. Normal operation
resumes after the feedback value leaves the deadband.
40.39 Set 1
deadband range
40.40 Set 1 deadband delay
Setpoint
Feedback
PID controller
output
PID controller
output frozen
Time
Set 1 deadband
range
40.39
1 = 1 / 10 = 1
Deadband range.
0.0 ... 32767.0
0.0 s / real32
Delay for the deadband. See parameter
.
Set 1 deadband
delay
40.40
1 = 1 s / 10 = 1 s
Delay for deadband area.
0.0 ... 3600.0 s
Not selected / uint16
Selects the mode of the sleep function.
See also section
Process PID control (page 109)
Set 1 sleep mode
40.41
0
Sleep function disabled.
Not selected
1
The output of the PID controller is compared to the
value of
.
If the PID controller output remains below the sleep
level longer than the sleep delay (
), the drive enters sleep mode.
Parameters
…
are in force.
Internal
2
The sleep function is activated by the source selected
by parameter
.
Parameters
…
and
are in force.
External
Not selected / uint32
Defines a source that is used to activate the PID sleep
function when parameter
is set
to
0 = Sleep function disabled
1 = Sleep function activated
Set 1 sleep enable
40.42
0
0
Not selected
1
1
Selected
Parameters 429
Summary of Contents for ACS880 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Page 2: ......
Page 4: ......
Page 16: ...16 ...
Page 22: ...22 ...
Page 24: ...24 ...
Page 44: ...44 ...
Page 66: ...66 ...
Page 148: ...148 ...
Page 168: ...168 ...
Page 704: ...704 ...
Page 728: ...728 ...
Page 742: ...742 ...
Page 762: ...762 ...