What to do
Cause
Event name /
Aux. code
Code
(hex)
Check the external 24 V DC power
supply to the control unit, or change
the setting of parameter
is set to
but no voltage is
connected to the XPOW connector of
the control unit.
External
power signal
missing
AFEC
Informative warning.
Motor ID run will occur at next start,
or is in progress.
Identification
run selected
AFF6
Informative warning.
Autophasing will occur at next start.
Autophasing
AFF7
Check safety circuit connections. For
more information, see appropriate
Safe torque off function is active, i.e.
safety circuit signal(s) connected to
connector XSTO is lost.
STO event
B5A0
drive hardware manual and
description of parameter
Informative event.
The drive has been powered up.
Power up
B5A2
Informative event.
ID run completed.
ID run done
B5F6
The auxiliary code specifies the type
of ID run.
0: None
1: Normal
2: Reduced
3: Standstill
4: Autophasing
5: Current measurement calibration
6: Advanced
7: Advanced standstill
Contact your local ABB representative,
quoting the auxiliary code. If the Drive
SW internal malfunction.
SW internal
diagnostics
B680
Composer tool is available, also create
and send a ‘support package’ (see
Drive composer manual for
instructions).
See
.
The calculated parameter checksum
does not match any enabled reference
checksum.
Checksum
mismatch
B686
Check motor and motor cables.
Maximum number of cleaning in the
defined time frame has been
exceeded.
Cleaning max
fault
D100
Check parameters
to
for
clean maximum protection settings.
Check parameters
and
Overload supervision signal exceeded
the defined overload supervision limit.
Overload
D101
Check parameters in group
.
Underload supervision signal exceeded
the defined underload supervision
limit.
Underload
D102
Check the source of the fault
(parameter
Fault generated by the signal
supervision 4 function.
Signal
supervision 3
D103
Check the source of the fault
(parameter
Fault generated by the signal
supervision 5 function.
Signal
supervision 3
D104
Fault tracing 691
Summary of Contents for ACS880 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Page 2: ......
Page 4: ......
Page 16: ...16 ...
Page 22: ...22 ...
Page 24: ...24 ...
Page 44: ...44 ...
Page 66: ...66 ...
Page 148: ...148 ...
Page 168: ...168 ...
Page 704: ...704 ...
Page 728: ...728 ...
Page 742: ...742 ...
Page 762: ...762 ...