Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
Distributed I/O bus settings.
I/O bus
configuration
206
This group is only visible with a BCU control unit.
This group contain parameters related to the
distributed I/O bus, which is used with some drives for
monitoring the cooling fans of the cabinet system. For
details, refer to
CIO-01 I/O module for distributed I/O
bus control user’s manual (3AXD50000126880
[English]).
No / uint16
Enables/disables the use of distributed I/O bus.
I/O bus enable
206.1
0
Distributed I/O bus is disabled.
1
Distributed I/O bus is enabled.
75.0% / real32
Defines the warning limit for fan speed. When fan speed
is below the value given with this parameter (in relation
Fan speed warning
limit
206.6
to requested reference), the control program generates
warning AE92 Fan speed. Parameter value 0 means that
no warning will be generated.
1% / 10%
Warning limit for fan speed.
0.0 ... 100.0%
50.0% / real32
Defines the fault limit for fan speed. When fan speed
is below the value given with this parameter (in relation
Fan speed fault limit
206.7
to requested reference), the control program generates
fault 8E12 Fan speed. Parameter value 0 means that no
fault will be generated.
1% / 10%
Fault limit for fan speed.
0.0 ... 100.0%
90000 h / uint32
Defines the warning limit for fan lifetime. When the fan
has been running longer (in hours) than the value given
Fan on-time warning
limit
206.8
with this parameter, the control program generates
warning AE91 Fan lifetime exceeded.
1 h / 1 h
Warning limit for fan lifetime.
0...596523 h
2 s / uint16
Defines a timeout for monitoring a node. The control
program monitors whether an active node can not be
Communication loss
time
206.9
found on the I/O us. If a communication break lasts
longer than the timeout, the control program generates
warning AE90 I/O bus communication.
1 s / 1 s
Communication loss time.
0...600 s
- / uint16
Activates communication for nodes 1…16.
Node activation
206.18
1 = Node 1 is active.
b0
1 = Node 2 is active.
b1
1 = Node 3 is active.
b2
1 = Node 4 is active.
b3
1 = Node 5 is active.
b4
1 = Node 6 is active.
b5
1 = Node 7 is active.
b6
1 = Node 8 is active.
b7
1 = Node 9 is active.
b8
1 = Node 10 is active.
b9
632 Parameters
Summary of Contents for ACS880 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Page 2: ......
Page 4: ......
Page 16: ...16 ...
Page 22: ...22 ...
Page 24: ...24 ...
Page 44: ...44 ...
Page 66: ...66 ...
Page 148: ...148 ...
Page 168: ...168 ...
Page 704: ...704 ...
Page 728: ...728 ...
Page 742: ...742 ...
Page 762: ...762 ...