Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
1
The master can only be started if all followers are ready
to operate (bit 1 of
in each
follower is on).
MSW bit 1
2
The master can only be started if all followers are ready
to switch on and ready to operate (bits 0 and 1 of
in each follower are on).
MSW bits 0 + 1
3
The starting of the master is not interlocked to the
status of the followers.
Always
4
The master can only be started if user-definable bit 12
of
in each follower is on. See
parameter
.
MSW bit 12
5
The master can only be started if both bit 0 and bit 12
of
in each follower are on.
MSW bits 0 + 12
6
The master can only be started if both bit 1 and bit 12
of
in each follower are on.
MSW bits 1 + 12
- / uint16
Parameters
are only effective when the
drive is the master on a D2D (drive-to-drive) link,
implemented by application programming. See
parameters
and
, and
Drive (IEC 61131-3) application
programming manual (3AUA0000127808 [English]).
In the master, parameters
and
60.20 M/F comm supervision sel 2
specify the
followers that are monitored for loss of communication.
This parameter selects which followers (out of followers
1…16) are monitored. Each of the selected followers is
polled by the master. If no reply is received, the action
specified in
is taken.
The status of communication is shown by
and
M/F comm
supervision sel 1
60.19
1 = Follower 1 is polled by the master.
Follower 1
b0
1 = Follower 2 is polled by the master.
Follower 2
b1
1 = Follower 3 is polled by the master.
Follower 3
b2
1 = Follower 4 is polled by the master.
Follower 4
b3
1 = Follower 5 is polled by the master.
Follower 5
b4
1 = Follower 6 is polled by the master.
Follower 6
b5
1 = Follower 7 is polled by the master.
Follower 7
b6
1 = Follower 8 is polled by the master.
Follower 8
b7
1 = Follower 9 is polled by the master.
Follower 9
b8
1 = Follower 10 is polled by the master.
Follower 10
b9
1 = Follower 11 is polled by the master.
Follower 11
b10
1 = Follower 12 is polled by the master.
Follower 12
b11
1 = Follower 13 is polled by the master.
Follower 13
b12
1 = Follower 14 is polled by the master.
Follower 14
b13
494 Parameters
Summary of Contents for ACS880 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Page 2: ......
Page 4: ......
Page 16: ...16 ...
Page 22: ...22 ...
Page 24: ...24 ...
Page 44: ...44 ...
Page 66: ...66 ...
Page 148: ...148 ...
Page 168: ...168 ...
Page 704: ...704 ...
Page 728: ...728 ...
Page 742: ...742 ...
Page 762: ...762 ...