Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
Settings for the frequency reference chain.
Frequency
reference chain
28
See the control chain diagrams
and
.
- / real32
Displays the used frequency reference before ramping.
See the control chain diagram on page
Frequency ref ramp
input
28.1
This parameter is read-only.
- / -
Frequency reference before ramping. For scaling, see
parameter
.
-598.00 ... 598.00 Hz
- / real32
Displays the final frequency reference (after selection,
limitation and ramping). See the control chain diagram
on page
.
Frequency ref ramp
output
28.2
This parameter is read-only.
- / -
Final frequency reference. For scaling, see parameter
-598.00 ... 598.00 Hz
P.9.21 / uint32
Selects frequency reference source 1.
Two signal sources can be defined by this parameter
and
. A digital source
Frequency ref1
source
28.11
selected by
28.14 Frequency ref1/2 selection
can be
used to switch between the two sources, or a
mathematical function (
)
applied to the two signals to create the reference.
…
…
0
AI
FB
Other
28.11
28.12
28.13
28.90
28.91
28.14
28.92
Ref1
ADD
SUB
MUL
MIN
MAX
0
AI
FB
Other
0
1
0
None.
Zero
1
12.12 AI1 scaled value (page 226)
AI1 scaled
2
12.22 AI2 scaled value (page 228)
.
AI2 scaled
4
3.5 FB A reference 1 (page 179)
FB A ref1
5
3.6 FB A reference 2 (page 179)
FB A ref2
8
3.9 EFB reference 1 (page 179)
.
EFB ref1
9
3.10 EFB reference 2 (page 179)
.
EFB ref2
10
3.11 DDCS controller ref 1 (page 179)
.
DDCS ctrl ref1
11
3.12 DDCS controller ref 2 (page 179)
DDCS ctrl ref2
12
3.13 M/F or D2D ref1 (page 180)
.
M/F reference 1
13
3.14 M/F or D2D ref2 (page 180)
M/F reference 2
Parameters 347
Summary of Contents for ACS880 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Page 2: ......
Page 4: ......
Page 16: ...16 ...
Page 22: ...22 ...
Page 24: ...24 ...
Page 44: ...44 ...
Page 66: ...66 ...
Page 148: ...148 ...
Page 168: ...168 ...
Page 704: ...704 ...
Page 728: ...728 ...
Page 742: ...742 ...
Page 762: ...762 ...