What to do
Cause
Event name /
Aux. code
Code
(hex)
Reboot the control unit (using
parameter
Internal fault.
Task overload
6481
or by cycling power. If the problem
persists, contact your local ABB
representative.
Reboot the control unit (using
parameter
Internal fault.
Stack
overflow
6487
or by cycling power. If the problem
persists, contact your local ABB
representative.
Reboot the control unit (using
parameter
File read error.
Internal file
load
64A1
or by cycling power. If the problem
persists, contact your local ABB
representative.
Contact your local ABB representative.
Internal record load error.
Internal
record load
64A2
Check the auxiliary code. See actions
for each code below.
Application file incompatible or
corrupted.
Application
loading
64A3
Reduce the size of the application.
Not enough memory for the
application.
8006
Reduce the number of parameter
mappings.
See the drive-specific log generated
by Automation Builder.
Update the system library or
reinstall Automation Builder.
The application contains the wrong
system library version.
8007
See the drive-specific log generated
by Automation Builder.
In Automation Builder, give a “Clean”
command and reload the
application.
The application is empty.
8008
In Automation Builder, check
application task configuration, give
The application contains invalid
tasks.
8009
a “Clean all” command, and reload
the application.
Update the system library or
reinstall Automation Builder.
The application contains an
unknown target (system) library
function.
800A
See the drive-specific log generated
by Automation Builder.
Record the auxiliary codes of all active
licensing faults and contact your
Running the control program is
prevented either because a restrictive
Licensing
fault
64A5
product vendor for further
instructions.
license exists, or because a required
license is missing.
Check the auxiliary code (format XXXX
YYYY). “XXXX” specifies the number
Error running the adaptive program.
Adaptive
program
64A6
of the function block (0000 = generic
error). “YYYY” indicates the problem
(see actions for each code below).
Restore the template program or
download the program to the drive.
Program corrupted or block
non-existent.
000A
Check the inputs of the block.
Required block input missing.
000C
Fault tracing 663
Summary of Contents for ACS880 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Page 2: ......
Page 4: ......
Page 16: ...16 ...
Page 22: ...22 ...
Page 24: ...24 ...
Page 44: ...44 ...
Page 66: ...66 ...
Page 148: ...148 ...
Page 168: ...168 ...
Page 704: ...704 ...
Page 728: ...728 ...
Page 742: ...742 ...
Page 762: ...762 ...