Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
22
The output is used to feed an excitation current to 1…3
PTC sensors. See section
Force PTC excitation
23
The output is used to feed an excitation current to 1…3
Pt1000 sensors. See section
Force Pt1000
excitation
37
AO1 data storage
38
.
AO2 data storage
- / real32
(Visible when
=
Forced value that can be used instead of the selected
output signal. See parameter
.
AO1 force data
14.78
1000 = 1 mA / 1000 =
1 mA
Forced value of analog output AO1.
0.000 ... 22.000 mA
0.000 mA / real32
(Visible when
=
)
Forced value that can be used instead of the selected
output signal. See parameter
.
AO1 force data
14.78
1000 = 1 mA / 1000 =
1 mA
Forced value of analog output AO1.
0.000 ... 20.000 mA
0.100 s / real32
(Visible when
=
)
Defines the filtering time constant for analog output
AO1.
Unfiltered signal
Filtered signal
%
100
63
T
t
O = I × (1 - e
-t/T
)
I = filter input (step)
O = filter output
t = time
T = filter time constant
AO1 filter time
14.79
1000 = 1 s / 1000 = 1
s
Filter time constant.
0.000 ... 30.000 s
Parameters 259