![ABB ACS880 Series Firmware Manual Download Page 387](http://html.mh-extra.com/html/abb/acs880-series/acs880-series_firmware-manual_2617387.webp)
Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
1000 = 1 s / 1000 = 1
s
Signal filter time.
0.000 ... 30.000 s
0.00 / real32
Defines the lower limit for signal supervision 6.
Supervision 6 low
32.229
- / -
Low limit.
-21474830.00 ...
21474830.00
0.00 / real32
Defines the upper limit for signal supervision 6.
Supervision 6 high
32.330
- / -
Upper limit.
-21474830.00 ...
21474830.00
No action / uint16
Selects the mode of signal supervision function 7.
Determines how the monitored signal (parameter
) is compared to its lower
and upper limits (parameters
and
respectively). The action
is taken when the condition is fulfilled as selected in
parameter
Supervision 7 action
32.235
0
Signal supervision 7 is not in use.
Disabled
1
A warning (
) is generated.
Low
2
Action is taken whenever the signal rises above its
upper limit.
High
3
Action is taken whenever the absolute value of the
signal falls below its (absolute) lower limit.
Abs low
4
Action is taken whenever the absolute value of the
signal rises above its (absolute) upper limit.
Abs high
5
Action is taken whenever the signal falls below its low
limit or rises above its high limit.
Both
6
Action is taken whenever the absolute value of the
signal falls below its (absolute) low limit or rises above
its (absolute) high limit.
Abs both
No action / uint16
Selects the action that drive takes when the value
monitored by signal supervision 7 exceeds its limits.
Note: This parameter does not affect the status
indicated by
.
Supervision 7 action
32.236
0
No action taken.
No action
1
A warning (
) is generated.
Warning
2
The drive trips on
.
Fault
3
If running, the drive trips on
.
Fault if running
Zero / uint32
Selects the signal to be monitored by signal supervision
function 7.
Supervision 7 signal
32.237
0
None.
Zero
See
Terms and abbreviations (page 169)
Other [value]
0.000 s / real32
Defines a filter time constant for the signal monitored
by signal supervision 7.
Supervision 7 filter
time
32.238
Parameters 387
Summary of Contents for ACS880 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Page 2: ......
Page 4: ......
Page 16: ...16 ...
Page 22: ...22 ...
Page 24: ...24 ...
Page 44: ...44 ...
Page 66: ...66 ...
Page 148: ...148 ...
Page 168: ...168 ...
Page 704: ...704 ...
Page 728: ...728 ...
Page 742: ...742 ...
Page 762: ...762 ...