Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
ESP CW bit 2 / unit32
Defines the source for Backspin speed observer
function enable signal.
For further information on Backspin speed observer
function, see section
Backspin speed observer.
The function detects whether the motor is spinning
and prevents drive start command until passive motor
speed reduces down to speed region defined as safe
to restart by the user.
ABB recommends to always enable the restart delay
and run for at least several minutes alongside with the
backspin speed observer function.
Speed observer
enable
74.30
0
Backspin speed observer function is disabled.
Not selected
1
Backspin speed observer function is enabled.
Selected
2
Digital input DI1 (
, bit 0).
DI1
3
Digital input DI2 (
, bit 1).
DI2
4
Digital input DI3 (
, bit 2).
DI3
5
Digital input DI4 (
, bit 3).
DI4
6
Digital input DI5 (
, bit 4).
DI5
7
Digital input DI6 (
, bit 5).
DI6
10
Digital input/output DIO1 (
, bit
0).
DIO1
11
Digital input/output DIO2 (
, bit
1).
DIO2
12
Parameter
74.1 ESP control word (page 519)
, bit 2 status
controls enable/disable status of the function.
ESP CW bit 2
See
Terms and abbreviations (page 169)
Other [bit]
-7.00 Hz / real32
Defines top negative speed at which fly-start operation
is permitted.
Together with parameter
74.32 Restart speed limit high
,
safe-to-restart speed region is formed.
Restart speed limit
low
74.31
10 = 1 Hz / 100 = 1 Hz
Restart speed limit low.
-598.00 ... 0.00 Hz
7.00 Hz / real32
Defines top positive speed at which fly-start operation
is permitted.
Together with parameter
,
safe-to-restart speed region is formed.
Restart speed limit
high
74.32
10 = 1 Hz / 100 = 1 Hz
Restart speed limit high.
0.00 ... 598.00 Hz
30.0 s / real32
Defines the time period required for the motor speed
measured by the Backspin speed observer function to
stay within the safe-to-restart speed region before
user-start command is permitted.
Observer speed
check time
74.33
10 = 1 s / 1 = 1 s
Observer speed check time.
0.0 ... 32000.0 s
Parameters 521
Summary of Contents for ACS880 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Page 2: ......
Page 4: ......
Page 16: ...16 ...
Page 22: ...22 ...
Page 24: ...24 ...
Page 44: ...44 ...
Page 66: ...66 ...
Page 148: ...148 ...
Page 168: ...168 ...
Page 704: ...704 ...
Page 728: ...728 ...
Page 742: ...742 ...
Page 762: ...762 ...