Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
1 = 1
0000h…FFFFh
- / uint16
Displays the torque controller limitation status word.
This parameter is read-only.
*Only one out of bits 0…3, and one out of bits 9…13
can be on simultaneously. The bit typically indicates
the limit that is exceeded first.
Torque limit status
30.2
*1 = Intermediate DC circuit undervoltage
Undervoltage
b0
*1 = Intermediate DC circuit overvoltage
Overvoltage
b1
*1 = Torque is being limited by
or the source of
. See diagram on page
Minimum torque
b2
*1 = Torque is being limited by
or the source of
.
See diagram on page
.
Maximum torque
b3
1 = An inverter current limit (identified by bits 8…11) is
active
Internal current
b4
(With permanent magnet motors, synchronous
reluctance motors, and externally-excited synchronous
motors only)
1 = Maximum load angle limit is active, ie. the motor is
producing as much torque as possible
Maximum load angle
b5
(With asynchronous motors only)
1 = Motor pull-out limit is active, ie. the motor cannot
produce any more torque
Motor pullout
b6
Reserved
b7
1 = Input current is being limited by the main circuit
thermal limit
Thermal
b8
*1 = Maximum output current (I
MAX
) is being limited
Max current
b9
*1 = Output current is being limited by
User current
b10
*1 = Output current is being limited by a calculated
thermal current value
Thermal IGBT
b11
*1 = Output current is being limited because of
estimated IGBT temperature
IGBT
overtemperature
b12
*1 = Output current is being limited because of IGBT
junction to case temperature
IGBT overload
b13
Reserved
b14…15
1 = 1
0000h…FFFFh
358 Parameters
Summary of Contents for ACS880 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Page 2: ......
Page 4: ......
Page 16: ...16 ...
Page 22: ...22 ...
Page 24: ...24 ...
Page 44: ...44 ...
Page 66: ...66 ...
Page 148: ...148 ...
Page 168: ...168 ...
Page 704: ...704 ...
Page 728: ...728 ...
Page 742: ...742 ...
Page 762: ...762 ...