Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
Maximum torque 1 /
uint32
Selects a source that switches between two different
maximum torque limits.
0 = Maximum torque limit 1 defined by
is active
1 = Maximum torque limit selected by
is active
See also parameter
Maximum torque sel
30.25
0
0.
Maximum torque 1
1
1.
Maximum torque 2
source
2
Digital input DI1 (
, bit 0).
DI1
3
Digital input DI2 (
, bit 1).
DI2
4
Digital input DI3 (
, bit 2).
DI3
5
Digital input DI4 (
, bit 3).
DI4
6
Digital input DI5 (
, bit 4).
DI5
7
Digital input DI6 (
, bit 5).
DI6
10
Digital input/output DIO1 (
, bit
0).
DIO1
11
Digital input/output DIO2 (
, bit
1).
DIO2
See
Terms and abbreviations (page 169)
Other [value]
300.00 % / real32
Defines the maximum shaft power in motoring mode,
ie. when power is being transferred from the motor to
the machinery.
The value is given in percent of nominal motor power.
Power motoring
limit
30.26
1 = 1 % / 100 = 1 %
Maximum shaft power in motoring mode.
0.00 ... 600.00 %
-300.00 % / real32
Defines the maximum shaft power in generating mode,
ie. when power is being transferred from the machinery
to the motor. The value is given in percent of nominal
motor power.
Note: Do not set this parameter to 0% in an attempt
to prevent reverse rotation. In an open-loop application,
that is likely to prevent the motor from stopping
altogether. To prevent reverse rotation, use the
speed/frequency limits in this parameter group, or
parameters
.
Power generating
limit
30.27
1 = 1 % / 100 = 1 %
Maximum shaft power in generating mode.
-600.00 ... 0.00 %
Enable / uint16
Enables the overvoltage control of the intermediate
DC link.
Fast braking of a high inertia load causes the voltage
to rise to the overvoltage control limit. To prevent the
DC voltage from exceeding the limit, the overvoltage
controller automatically decreases the braking torque.
Note: With internal brake chopper, drive increases its
internal overvoltage control limit to enable higher
reliability in breaking.
Overvoltage control
30.30
0
Overvoltage control disabled.
Disable
364 Parameters
Summary of Contents for ACS880 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Page 2: ......
Page 4: ......
Page 16: ...16 ...
Page 22: ...22 ...
Page 24: ...24 ...
Page 44: ...44 ...
Page 66: ...66 ...
Page 148: ...148 ...
Page 168: ...168 ...
Page 704: ...704 ...
Page 728: ...728 ...
Page 742: ...742 ...
Page 762: ...762 ...