Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
Control of the supply unit of the drive, such as DC
voltage and reactive power reference.
LSU control
94
Note that the references defined here must also be
selected as the reference source in the supply control
program to be effective.
This group is only visible when supply unit control has
been activated by parameter
See also section
Control of a supply unit (LSU).
On / uint16
Enables/disables the internal INU-LSU state machine.
When the state machine is enabled, the inverter unit
(INU) controls the supply unit (LSU) and prevents the
inverter unit from starting until the supply unit is ready.
LSU Control
94.1
When the state machine is disabled, the status of the
supply unit is ignored by the inverter unit.
0
INU-LSU state machine disabled.
Off
1
INU-LSU state machine enabled.
On
Disable / uint16
Enables/disables control panel and PC tool access to
the supply unit (line-side converter) via the inverter unit
(motor-side converter).
LSU panel
communication
94.2
Note: This feature is only supported by the following
drives:
• ACS880-11
• ACS880-31
• ACS880-17 based on an integrated drive module
• ACS880-37 based on an integrated drive module.
0
Control panel and PC tool access to supply unit via
inverter unit disabled.
Disable
1
Control panel and PC tool access to supply unit via
inverter unit enabled.
Enable
ABB single drives
standard SW / uint16
(Only visible with certain drive types.)
Selects the functionality of bit 1 of
INU-LSU status word
profile
94.4
0
The drive sets bit 1 of
after the
DC link is charged.
ABB single drives
standard SW
1
The drive sets bit 1 of
after the
main contactor is closed and the supply unit (line-side
converter) is running.
Backwards
compatible SW
This setting can be used eg. when installing the drive
into an existing set-up with other ACS880 as well as
ACS800 drives.
Not selected / uint32
(Only visible when IGBT supply unit control activated
by
)
LSU external start
command
94.5
Selects the source for LSU external start command.
This parameter is visible only if INU-ISU communication
is enabled in 92.20 bit 15.
Note: If LSU is stopped using parameter
, LSU continues to run during
the time defined by
.
Parameters 589
Summary of Contents for ACS880 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Page 2: ......
Page 4: ......
Page 16: ...16 ...
Page 22: ...22 ...
Page 24: ...24 ...
Page 44: ...44 ...
Page 66: ...66 ...
Page 148: ...148 ...
Page 168: ...168 ...
Page 704: ...704 ...
Page 728: ...728 ...
Page 742: ...742 ...
Page 762: ...762 ...