STATE/Description
Value
Name
Bit
Fault reset if an active fault exists. Proceed to SWITCH-
ON INHIBITED.
0=>1
Reset
7
Note: This bit is effective only if the fieldbus interface
is set as the source of the reset signal by drive para-
meters.
Continue normal operation.
0
Accelerate to inching (jogging) setpoint 1.
1
Inching 1
8
Note:
•
Bits 4...6 must be 0.
•
See also section
.
Inching (jogging) 1 disabled.
0
Accelerate to inching (jogging) setpoint 2.
1
Inching 2
9
See notes at bit 8.
Inching (jogging) 2 disabled.
0
Fieldbus control enabled.
1
Remote cmd
10
Control word and reference not getting through to the
drive, except for bits 0...2.
0
Select External Control Location EXT2. Effective if
control location is parameterized to be selected from
fieldbus.
1
Ext ctrl loc
11
Select External Control Location EXT1. Effective if
control location is parameterized to be selected from
fieldbus.
0
Reserved.
12 to 15
736 Fieldbus control through a fieldbus adapter