No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
H1-41
(09EB) Terminal S1 Off-Delay
Time
Term S1 OffDelay
Sets the length of time needed for Terminal S1 to be open
before the drive removes the programmed function.
Default: 0.0 s
Min.: 0.0
Max.: 3000.0
–
H1-42
(09EC) Terminal S2 Off-Delay
Time
Term S2 OffDelay
Sets the length of time needed for Terminal S2 to be open
before the drive removes the programmed function.
Default: 0.0 s
Min.: 0.0
Max.: 3000.0
–
H1-43
(09ED) Terminal S3 Off-Delay
Time
Term S3 OffDelay
Sets the length of time needed for Terminal S3 to be open
before the drive removes the programmed function.
Default: 0.0 s
Min.: 0.0
Max.: 3000.0
–
H1-44
(09EE) Terminal S4 Off-Delay
Time
Term S4 OffDelay
Sets the length of time needed for Terminal S4 to be open
before the drive removes the programmed function.
Default: 0.0 s
Min.: 0.0
Max.: 3000.0
–
H1-45
(09EF) Terminal S5 Off-Delay
Time
Term S5 OffDelay
Sets the length of time needed for Terminal S5 to be open
before the drive removes the programmed function.
Default: 0.0 s
Min.: 0.0
Max.: 3000.0
–
H1-46
(09F0) Terminal S6 Off-Delay
Time
Term S6 OffDelay
Sets the length of time needed for Terminal S6 to be open
before the drive removes the programmed function.
Default: 0.0 s
Min.: 0.0
Max.: 3000.0
–
H1-47
(09F4) Terminal S7 Off-Delay
Time
Term S7 OffDelay
Sets the length of time needed for Terminal S7 to be open
before the drive removes the programmed function.
Default: 0.0 s
Min.: 0.0
Max.: 3000.0
–
H1-48
(09F5) Terminal S8 Off-Delay
Time
Term S8 OffDelay
Sets the length of time needed for Terminal S8 to be open
before the drive removes the programmed function.
Default: 0.0 s
Min.: 0.0
Max.: 3000.0
–
H1 Multi-Function Digital Input Selections
H1-
oo
Setting
Function
LCD Display
Description
Page
0
3-Wire sequence
3-Wire Control
Closed: Reverse rotation (only if the drive is set up for 3-Wire sequence)
Terminals S1 and S2 are automatically set up for the Run command and Stop
command.
2
External reference 1/2
selection
Ext Ref Sel
Open: Run command and frequency reference source 1 (determined by b1-01 and
b1-02)
Closed: Run command and frequency reference source 2 (determined by b1-15
and b1-16)
–
3
Multi-Step Speed
Reference 1
Multi-Step Ref 1
When input terminals are set to Multi-Step Speed References 1 through 3,
switching combinations of those terminals will create a multi-step speed sequence
using the frequency references set in d1-01 through d1-08.
–
4
Multi-Step Speed
Reference 2
Multi-Step Ref 2
When input terminals are set to Multi-Step Speed References 1 through 3,
switching combinations of those terminals will create a multi-step speed sequence
using the frequency references set in d1-01 through d1-08.
–
5
Multi-Step Speed
Reference 3
Multi-Step Ref 3
When input terminals are set to Multi-Step Speed References 1 through 3,
switching combinations of those terminals will create a multi-step speed sequence
using the frequency references set in d1-01 through d1-08.
–
6
Jog reference selection
Jog Freq Ref
Closed: Jog frequency reference (d1-17) selected. Jog has priority over all other
reference sources.
–
7
Accel/decel time
selection 1
Multi-Acc/Dec 1
Used to switch between accel/decel time 1 (set in C1-01, C1-02) and accel/decel
time 2 (set in C1-03, C1-04).
–
8
Baseblock command
(N.O.)
Ext BaseBlk N.O.
Closed: No drive output
–
9
Baseblock command
(N.C.)
Ext BaseBlk N.C.
Open: No drive output
–
A
Accel/decel ramp hold
Acc/Dec RampHold
Open: Accel/decel is not held
Closed: The drive pauses during acceleration or deceleration and maintains the
output frequency.
–
B
Drive overheat alarm
(oH2)
OH2 Alarm Signal
Closed: Closes when an oH2 alarm occurs
–
B.8 H Parameters: Multi-Function Terminals
YASKAWA TOEPYAIUPW01A YASKAWA AC Drive - U1000 iQpump Matrix Drive User Manual
301
B
Parameter List