n
H5-04: Stopping Method after Communication Error
Selects the stopping method after a MEMOBUS/Modbus communications error (CE) has occurred.
No.
Name
Setting Range
Default
H5-04
Stopping Method after CE
0 to 4
3
Setting 0: Ramp to stop (uses the deceleration time currently enabled)
Setting 1: Coast to stop
Setting 2: Fast Stop
Setting 3: Alarm only (continue operation)
Setting 4: Run at H5-14
This setting will trigger a “CE – Comm Loss” alarm and cause the drive to run at the speed set in H5-14 speed when a
Communication Error (CE) occurs.
The drive faults on CE and coasts to stop when H5-15 > 0 and the CE condition persists for the time set in H5-15.
Note the following conditions when using this setting and a CE occurs:
• During Pre-charge, the drive will continue to run at the Pre-charge frequency
• During Sleep, the drive will wake up and run at the speed set in H5-14
• During Feedback Drop, the drive will wake up an run at the speed set in H5-14
• Lag pumps are deactivated when in Contactor Multiplex.
n
H5-05: Communication Fault Detection Selection
Enables or disables the CE detection for communications.
No.
Name
Setting Range
Default
H5-05
Communication Fault Detection Selection
0 or 1
1
Setting 0: Disabled
No communication error detection. The drive continues operation.
Setting 1: Enabled
If the drive does not receive data from the master for longer than the time set to H5-09, then a CE fault will be triggered and
the drive will operate as determined by parameter H5-04.
n
H5-06: Drive Transmit Wait Time
Sets the time the drive waits after receiving data from a master until responding data.
Note:
Cycle power for the setting to take effect.
No.
Name
Setting Range
Default
H5-06
Drive Transmit Wait Time
5 to 65 ms
5 ms
Command message
Response message
Command message
PLC→Drive
PLC→Drive
Drive→PLC
Time
24 bit length H5-06 setting
Figure C.5 Drive Transmit Wait Time Setting
n
H5-07: RTS Control Selection
Enables or disables RTS control.
Note:
Cycle power for the setting to take effect.
No.
Name
Setting Range
Default
H5-07
RTS Control Selection
0 or 1
1
C.4 MEMOBUS/Modbus Setup Parameters
378