3006: General HOA Keys
x
AUTO Run = AUTO key + S1,
Speed = A2
HAND1 Run = S6,
Speed = P5-02
or Operator when P5-01 = 1,
otherwise Terminal A1
HAND2 Run = S7,
Speed = P5-05 or Operator
Run
Fault
Reset
HAND1
HAND2
Comms Run
Drive
Serial Comms
AUTO Speed Ref
Def: 4 to 20 mA (H3-09)
P5-01 = 0
HAND1 Speed Ref
Def: 0 to 10 V (H3-01)
Ext. Pump
Fault (N.O.)
Ext. Pump
Fault (N.O.)
Ext. Pump
Fault (N.O.)
S1
S2
S3
S4
S5
S6
S7
S8
SN
24V
+V
A1
A2
A3
AC
R+
R- S+ S-
Switch to Net Coms = S8;
AUTO Run = Auto key + Serial Run,
Speed = Serial Comms
Figure 4.15 Default Port Configuration for General HOA Keys
Parameters Set Depending on A1-08 Setting
The following table shows the parameters that are set depending on the A1-08 initialization:
A1-08 = 3005
(A1-06 = 5)
General Ext HOA
A1-08 = 3006
(A1-06 = 6)
General HOA Keys
Parameter
Value
Parameter
Value
A1-02
0
A1-02
0
b1-01
1
b1-01
1
b1-02
1
b1-02
6
b1-03
0
b1-03
0
b1-15
2
b1-15
2
b1-16
2
b1-16
7
b5-01
0
b5-01
0
C1-01
25.0 s
C1-01
25.0 s
C1-02
25.0 s
C1-02
25.0 s
H1-02
26H
H1-02
26H
H1-05
26H
H1-05
26H
H1-08
2
H1-08
2
H2-01
0H
H2-01
0H
H2-02
AH
H2-02
AH
H3-02
20H
H3-02
20H
4.7 Basic U1000 iQpump Setup and Application Preset Parameters
142
YASKAWA TOEPYAIUPW01A YASKAWA AC Drive - U1000 iQpump Matrix Drive User Manual