Table A.2 Power Ratings (Three-Phase 200 V Class) Continued
Item
Specification
Drive Model
2
o
0104
2
o
0130
2
o
0154
2
o
0192
2
o
0248
Maximum Applicable
Motor Capacity kW (HP)
30 (40)
37 (50)
45 (60)
55 (75)
75 (100)
Input/Output
Rating
95
118
140
175
226
43
54
64
80
103
104
130
154
192
248
Overload Tolerance
Rating: 120% of rated output current for 60 s
(Derating may be required for applications that start and stop frequently)
Carrier Frequency
4 kHz (User adjustable up to 8 kHz. Derating may be required.)
4 kHz
Maximum Output Voltage (V)
Proportional to input voltage
Maximum Output Frequency (Hz)
400 Hz (User-adjustable)
Power Supply
Rated Voltage
Rated Frequency
Three-phase 200 to 240 Vac 50/60 Hz
Allowable Voltage Fluctuation
-15 to 10%
Allowable Frequency Fluctuation
±3% (Frequency fluctuation rate: 1 Hz/100 ms or less)
Allowable Phase Power Supply Voltage
Unbalance
2% or less
5% or less (IEEE519 compliant)
Input Power Factor
0.98 or more (During rated operation)
connections, and power supply impedance.
<3> Rated input capacity is calculated with a power line voltage of 240 V × 1.1.
<4> The rated output current of the drive should be equal to or greater than the motor rated current.
<5> Carrier frequency is set to 4 kHz. Current derating is required to raise the carrier frequency.
<6> Commercial power mode results in near zero input harmonics. Existing power conditions and operation mode can affect input harmonics.
A.1 Power Ratings
YASKAWA TOEPYAIUPW01A YASKAWA AC Drive - U1000 iQpump Matrix Drive User Manual
265
A
Specifications