E1-05 and E1-13 are automatically set to the same value.
u
E2: Motor 1 Parameters
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
E2-01
(030E) Motor Rated Current
Motor Rated FLA
Sets the motor nameplate full load current in amps.
Automatically set during Auto-Tuning.
Default:
Min.: 10% of
drive rated
current
Max.: 150% of
drive rated
current
E2-02
(030F) Motor Rated Slip
Motor Rated Slip
Sets the motor rated slip. Automatically set during
Auto-Tuning.
Default:
Min.: 0.00 Hz
Max.: 20.00 Hz
–
E2-03
(0310)
Motor No-Load Current No-Load Current
Sets the no-load current for the motor. Automatically set during
Auto-Tuning.
Default:
Min.: 0.00 A
Max.: E2-01
–
E2-04
(0311)
Number of Motor Poles Number of Poles
Sets the number of motor poles. Automatically set during
Auto-Tuning.
Default: 2
Min.: 2
Max.: 48
–
E2-05
(0312)
Motor Line-to-Line
Resistance
Term Resistance
Sets the phase-to-phase motor resistance. Automatically set
during Auto-Tuning.
Default:
Min.: 0.000 Ω
Max.: 65.000 Ω
–
E2-06
(0313)
Motor Leakage
Inductance
Leak Inductance
Sets the voltage drop due to motor leakage inductance as a
percentage of motor rated voltage. Automatically set during
Auto-Tuning.
Default:
Min.: 0.0%
Max.: 40.0%
–
E2-07
(0314)
Motor Iron-Core
Saturation Coefficient 1 Saturation Comp1
OLV
OLV
OLV
OLV
Sets the motor iron saturation coefficient at 50% of magnetic
flux. Automatically set during Auto-Tuning.
Default: 0.50
Min.: 0.00
Max.: 0.50
–
E2-08
(0315)
Motor Iron-Core
Saturation Coefficient 2 Saturation Comp2
OLV
OLV
OLV
OLV
Sets the motor iron saturation coefficient at 75% of magnetic
flux. Automatically set during Auto-Tuning.
Default: 0.75
Min.: E2-07
Max.: 0.75
–
E2-09
(0316)
Motor Mechanical Loss Mechanical Loss
OLV
OLV
OLV
OLV
Sets the motor mechanical loss as a percentage of motor rated
power (kW).
Default: 0.0%
Min.: 0.0
Max.: 10.0
–
E2-10
(0317)
Motor Iron Loss for
Torque Compensation
Motor Iron Loss
Sets the motor iron loss.
Default:
Min.: 0 W
Max.: 65535 W
–
E2-11
(0318)
Motor Rated Power
Mtr Rated Power
Sets the motor rated power in kilowatts (1 HP = 0.746 kW).
Automatically set during Auto-Tuning.
Default:
Min.: 0.00 kW
Max.: 650.00 kW
–
E2-20
(1103)
Motor Service Factor
Amps
Motor SF Amps
Sets the Motor Overload Current level for oL1 fault.
When parameter is set to 0, Motor Rated Current (E2-01) is
used instead for the oL1 fault calculation.
Default: 0.00 A
Range:
–
<1> Default setting is dependent on parameter o2-04, Drive Model Selection.
<2> Display is in the following units:
<4> Default resolution is dependent on drive size.
B.6 E: Motor Parameters
YASKAWA TOEPYAIUPW01A YASKAWA AC Drive - U1000 iQpump Matrix Drive User Manual
293