Setting
Function
Page
A4
Pre-Charge
–
A5
Anti-Jam Active
–
A6
De-Scale Active
–
A7
Flow Rate Limit
A9
Thrust Mode
–
Setting
Function
Page
AA
Utility Start Delay
–
AB
Main FdBk Lost
–
AC
Backup FdBk Lost
–
100 to
1AC
Function 0 to AC with inverse output
–
Setting 30: During Torque Limit
The output closes when the motor is operating at the torque limit specified by the L7-
oo
parameters or an analog input. This
setting can only be used in OLV control mode.
Setting 42: Pressure Reached
Pressure Setpoint has been reached. Activation and deactivation conditions based on the Pressure Feedback and the settings
of P4-36 to P4-40.
Direct-acting PID
The terminal activates when the feedback meets or exceeds the setpoint for the time set in P4-38.
The terminal deactivates based on the hysteresis level (P4-37), delay time (P4-39), and the pressure reached exit conditions
(P4-36).
When P4-36 = 0 (Hysteresis Above & Below), the terminal deactivates when the feedback falls below the setpoint – hysteresis
level or when it rises above the se hysteresis level for the time set in P4-39.
When P4-36 = 1 (Hysteresis 1-Way), the terminal only deactivates when the feedback falls below the setpoint – hysteresis
level for the time set in P4-39.
Inverse-acting PID
The terminal activates when he feedback meets or falls below the setpoint for the time set in P4-20.
The terminal deactivates based on the hysteresis level (P4-37), delay time (P4-39), and the pressure reached exit conditions
(P4-36).
When P4-36 = 0 (Hysteresis Above & Below), the terminal deactivates when the feedback falls below the setpoint – hysteresis
level or when it rises above the se hysteresis level for the time set in P4-39.
When P4-36 = 1 (Hysteresis 1-Way), the terminal only deactivates when the feedback rises above the se hysteresis
level for the time set in P4-39.
n
H3-01: Terminal A1 Signal Level Selection
Selects the input signal level for analog input A1.
No.
Name
Setting Range
Default
H3-01
Terminal A1 Signal Level Selection
0 to 3
0
Setting 0: 0 to 10 Vdc
The input level is 0 to 10 Vdc. The minimum input level is limited to 0%, so that a negative input signal due to gain and bias
settings will be read as 0%.
Setting 1: 0 to 10 Vdc Bipolar
The input level is -10 to 10 Vdc. If the resulting voltage is negative after being adjusted by gain and bias settings, then the
motor will rotate in reverse.
Setting 2: 4 to 20 mA
Setting 3: 0 to 20 mA
n
H3-02: Terminal A1 Function Selection
Selects the input signal level for analog input A1.
No.
Name
Setting Range
Default
H3-02
Terminal A1 Function Selection
0 to 26
0
4.7 Basic U1000 iQpump Setup and Application Preset Parameters
154