HOA Keypad Display
Minor Fault Name
oH2
Drive Overheat Warning
“Drive Overheat Warning” was input to a multi-function input terminal, S1 through S8 (H1-
oo
= B).
Cause
Possible Solution
An external device triggered an overheat
warning in the drive.
Search for the device that tripped the overheat warning. Remove the cause of the problem.
HOA Keypad Display
Minor Fault Name
oH3
Motor Overheat
The motor overheat signal entered to a multi-function analog input terminal exceeded the alarm level (H3-02,
H3-06 or H3-10 = E).
Cause
Possible Solutions
Motor thermostat wiring is faulty (PTC
input).
Repair the PTC input wiring.
There is a fault on the machine side (e.g.,
the machine is locked up).
• Check the status of the machine.
• Remove the cause of the fault.
Motor has overheated.
• Check the load size, accel/decel times, and cycle times.
• Decrease the load.
• Increase accel and decel times (C1-01 to C1-04).
• Adjust the preset V/f pattern (E1-04 through E1-10). This involves reducing E1-08 and E1-10.
Note:
Refrain from lowering E1-08 and E1-10 excessively to prevent a reduction in load tolerance
at low speeds.
• Check the motor-rated current.
• Enter motor-rated current on motor nameplate (E2-01).
• Ensure the motor cooling system is operating normally.
• Repair or replace the motor cooling system.
HOA Keypad Display
Minor Fault Name
oL1
Motor Overload
The electronic motor overload protection tripped
Cause
Possible Solution
Load is too heavy
Reduce the load.
Cycle times are too short during
acceleration and deceleration
Increase the acceleration and deceleration times (C1-01 through C1-04).
A general-purpose motor is driven below
the rated speed with a high load
• Reduce the load.
• Increase the speed.
• If the motor is supposed to operate at low speeds, either increase the motor capacity or use a motor
specifically designed to operate in the desired speed range.
The output voltage is too high
• Adjust the user-set V/f pattern (E1-04 through E1-10) by reducing E1-08 and E1-10.
• Do not set E1-08 and E1-10 too low. This reduces load tolerance at low speeds.
The wrong motor rated current is set to
E2-01
• Check the motor-rated current.
• Enter the motor rated current to parameter E2-01 as indicated on the motor nameplate.
The base frequency is set incorrectly
• Check the rated frequency indicated on the motor nameplate.
• Enter the rated frequency to E1-06 (Base Frequency).
The electrical thermal protection
characteristics and motor overload
characteristics do not match
• Check the motor characteristics.
• Correct the type of motor protection that has been selected (L1-01).
• Install an external thermal relay.
The electrical thermal relay is operating at
the wrong level
• Check the current rating listed on the motor nameplate.
• Check the value set for the motor rated current (E2-01).
Motor overheated by overexcitation
operation
• Overexcitation increases the motor loss and the motor temperature. Excessive duration of overexcitation
may cause motor damage. Prevent excessive overexcitation operation or apply proper cooling to the motor.
• Reduce the excitation deceleration gain (n3-13).
• Set L3-04 (Stall Prevention during Deceleration) to a value other than 4.
Parameters related to Speed Search are set
incorrectly
• Check values set to Speed Search related parameters.
• Adjust the Speed Search current and Speed Search deceleration times (b3-02 and b3-03 respectively).
• After Auto-Tuning, set b3-24 to 1 to enable Speed Estimation Speed Search.
5.4 Alarm Detection
208
YASKAWA TOEPYAIUPW01A YASKAWA AC Drive - U1000 iQpump Matrix Drive User Manual