Drive
Model
Terminal
For USA and Canada
For South America
Screw
Size
Tightening
Torque
N·m (lb.in.)
Recomm. Gauge
mm
2
(AWG, kcmil)
Wire Range
mm
2
(AWG, kcmil)
Recomm. Gauge
mm
2
(AWG, kcmil)
Wire Range
mm
2
(AWG, kcmil)
4
o
0180
R/L1, S/L2, T/L3
35 × 2
(2 × 2P)
25 to 95 × 2
(3 to 4/0 × 2P)
25 × 2P
(3 × 2P)
25 to 95 × 2P
(3 to 4/0 × 2P)
M10
15 to 20
(130 to 173)
U/T1, V/T2, W/T3
35 × 2
(2 × 2P)
25 to 95 × 2
(3 to 4/0 × 2P)
25 × 2P
(3 × 2P)
25 to 95 × 2P
(3 to 4/0 × 2P)
M10
25
(3)
25 to 70
(4 to 2/0)
25
(3)
25 to 70
(3 to 2/0)
M10
17.7 to 22.6
(156 to 200)
p1, n1
2.5
(14)
2.5 to 4
(14 to 12)
2.5
(14)
2.5 to 4
(14 to 12)
M4
1.2 to 2.0
(10.4 to 17.4)
4
o
0216
R/L1, S/L2, T/L3
50 × 2
(1/0 × 2P)
35 to 95 × 2
(2 to 4/0 × 2P)
35 × 2P
(1 × 2P)
25 to 95 × 2P
(3 to 4/0 × 2P)
M10
15 to 20
(130 to 173)
U/T1, V/T2, W/T3
50 × 2
(1/0 × 2P)
35 to 95 × 2
(2 to 4/0 × 2P)
35 × 2P
(1 × 2P)
25 to 95 × 2P
(3 to 4/0 × 2P)
M10
25
(3)
25 to 95
(4 to 4/0)
35
(1)
25 to 95
(3 to 4/0)
M12
31.4 to 39.2
(278 to 347)
p1, n1
2.5
(14)
2.5 to 4
(14 to 12)
2.5
(14)
2.5 to 4
(14 to 12)
M4
1.2 to 2.0
(10.4 to 17.4)
4
o
0240
R/L1, S/L2, T/L3
50 × 2
(1/0 × 2P)
50 to 95 × 2
(1/0 to 4/0 × 2P)
50 × 2P
(1/0 × 2P)
35 to 95 × 2P
(1 to 4/0 × 2P)
M10
15 to 20
(130 to 173)
U/T1, V/T2, W/T3
50 × 2
(1/0 × 2P)
50 to 95 × 2
(1/0 to 4/0 × 2P)
50 × 2P
(1/0 × 2P)
35 to 95 × 2P
(1 to 4/0 × 2P)
M10
35
(2)
35 to 95
(2 to 4/0)
50
(1/0)
35 to 95
(1 to 4/0)
M12
31.4 to 39.2
(278 to 347)
p1, n1
2.5
(14)
2.5 to 4
(14 to 12)
2.5
(14)
2.5 to 4
(14 to 12)
M4
1.2 to 2.0
(10.4 to 17.4)
4
o
0302
R/L1, S/L2, T/L3
70 × 2
(3/0 × 2P)
50 to 95 × 2
(1/0 to 4/0 × 2P)
70 × 2P
(3/0 × 2P)
50 to 95 × 2P
(1/0 to 4/0 × 2P)
M10
15 to 20
(130 to 173)
U/T1, V/T2, W/T3
70 × 2
(3/0 × 2P)
50 to 95 × 2
(1/0 to 4/0 × 2P)
70 × 2P
(3/0 × 2P)
50 to 95 × 2P
(1/0 to 4/0 × 2P)
M10
35
(1)
35 to 150
(1 to 300)
70
(3/0)
35 to 150
(1 to 300)
M12
31.4 to 39.2
(278 to 347)
p1, n1
2.5
(14)
2.5 to 4
(14 to 12)
2.5
(14)
2.5 to 4
(14 to 12)
M4
1.2 to 2.0
(10.4 to 17.4)
4
o
0361
R/L1, S/L2, T/L3
95 × 2
(4/0 × 2P)
70 to 95 × 2
(3/0 to 4/0 × 2P)
95 × 2P
(4/0 × 2P)
70 to 95 × 2P
(3/0 to 4/0 × 2P)
M10
15 to 20
(130 to 173)
U/T1, V/T2, W/T3
95 × 2
(4/0 × 2P)
70 to 95 × 2
(3/0 to 4/0 × 2P)
95 × 2P
(4/0 × 2P)
70 to 95 × 2P
(3/0 to 4/0 × 2P)
M10
50
(1/0)
50 to 150
(1/0 to 300)
95
(4/0)
70 to 150
(3/0 to 300)
M12
31.4 to 39.2
(278 to 347)
p1, n1
2.5
(14)
2.5 to 4
(14 to 12)
2.5
(14)
2.5 to 4
(14 to 12)
M4
1.2 to 2.0
(10.4 to 17.4)
4
o
0414
R/L1, S/L2, T/L3
150 × 2
(300 × 2P)
95 to 150 × 2
(4/0 to 300 × 2P)
95 × 2P
(4/0 × 2P)
95 to 150 × 2P
(4/0 to 300 × 2P)
M12
25 to 35
(217 to 304)
U/T1, V/T2, W/T3
150 × 2
(300 × 2P)
95 to 150 × 2
(4/0 to 300 × 2P )
95 × 2P
(4/0 × 2P)
95 to 150 × 2P
(4/0 to 300 × 2P )
M12
50
(1/0)
50 to 240
(1/0 to 400)
95
(4/0)
70 to 240
(3/0 to 400)
M12
31.4 to 39.2
(278 to 347)
p1, n1
2.5
(14)
2.5 to 4
(14 to 12)
2.5
(14)
2.5 to 4
(14 to 12)
M4
1.2 to 2.0
(10.4 to 17.4)
u
Main Circuit Terminal and Motor Wiring
This section outlines the various steps, precautions, and checkpoints for wiring the main circuit terminals and motor terminals.
NOTICE: When connecting the motor to the drive output terminals U/T1, V/T2, and W/T3, the phase order for the drive and motor should
match. Failure to comply with proper wiring practices may cause the motor to run in reverse if the phase order is backward.
NOTICE: Route motor leads U/T1, V/T2, and W/T3 separate from all other leads to reduce possible interference related issues. Failure to
comply may result in abnormal operation of drive and nearby equipment.
3.8 Main Circuit Wiring
YASKAWA TOEPYAIUPW01A YASKAWA AC Drive - U1000 iQpump Matrix Drive User Manual
71
3
Electrical Installation