No.
(Addr.
Hex)
Name
LCD Display
Description
Analog
Output Level
Unit
U1-12
(004B) Drive Status
Int Ctl Sts 1
Displays the drive operation status.
U1 - 12=
00000000
During run
During zero-speed
During REV
During fault reset
signal input
During speed agree
Drive ready
During alarm
detection
During fault detection
1
1
1
1
1
1
1
1
No signal output
available
–
U1-13
(004E) Terminal A1 Input Level Term A1 Level
Displays the signal level to analog input terminal A1.
10 V: 100%
(-10 to +10 V)
0.1%
U1-14
(004F) Terminal A2 Input Level Term A2 Level
Displays the signal level to analog input terminal A2.
10 V: 100%
(-10 to +10 V)
0.1%
U1-15
(0050) Terminal A3 Input Level Term A3 Level
Displays the signal level to analog input terminal A3.
10 V: 100%
(-10 to +10 V)
0.1%
U1-16
(0053)
Output Frequency after
Soft Starter
SFS Output
Displays output frequency with ramp time and S-curves. Units
determined by o1-03.
10 V: Max.
frequency
(-10 to +10 V)
0.01 Hz
U1-18
(0061) oPE Fault Parameter
OPE Error Code
Displays the parameter number that caused the oPE02 or oPE08
operation error.
No signal output
available
–
U1-19
(0066)
MEMOBUS/Modbus
Error Code
Transmit Err
Displays the contents of a MEMOBUS/Modbus error.
U1 - 19=
00000000
CRC Error
Data Length Error
Not Used
Parity Error
Overrun Error
Framing Error
Timed Out
Not Used
1
1
0
1
1
1
1
0
No signal output
available
–
U1-24
(007D) Input Pulse Monitor
Term RP Inp Freq
Displays the frequency to pulse train input terminal RP.
Determined by
H6-02
1 Hz
U1-25
(004D)
Software Number
(Flash)
CPU 1 SW Number
FLASH ID
No signal output
available
–
U1-26
(005B) Software No. (ROM)
CPU 2 SW Number
ROM ID
No signal output
available
–
U1-54
(1083)
Drive Input Power
Voltage Effective Value Power Supply Volt
Displays the effective value of the drive input power voltage.
200 V class
10 V: 400 V
400 V class
10 V: 800 V
1 V
U1-58
(1087)
Power Supply
Frequency
Power Supply Freq
Displays the frequency of the drive input power supply.
10 V: Rated
frequency
0.1 Hz
U1-72
(1095)
Input Power Supply
Information
Power Supply Sts
Displays information on the input power supply.
U1 - 72=
00000000
Bit 0: AUv reset. (0: Not completed, 1: Reset)
Bit 1: PF reset (0: Not completed, 1: Reset)
Bit 2: Rated frequency detection
(0: Not completed, 1: Completed)
Bit 3: Phase order detection
(0: Not completed, 1: Completed)
Bit 4: Power supply established
(0: Not completed, 1: Completed)
Bit 5: Fdv detection (0: Not detected, 1: Detected)
Bit 6: PF detection (0: Not detected, 1: Detected)
Bit 7: Reserved.
No signal output
available
–
U1-75
(0851) Time-Hour/Minute
Time Hr Min HHMM Displays the current time (Hours and Minutes).
No signal output
available
–
B.16 U: Monitors
354
YASKAWA TOEPYAIUPW01A YASKAWA AC Drive - U1000 iQpump Matrix Drive User Manual