H3 Multi-Function Analog Input Settings
H3-
oo
Setting
Function
LCD Display
Description When Output Is 100%
Page
D
Frequency bias
Freq Ref Bias 2
10 V = E1-04 (maximum output frequency)
–
E
Motor temperature
(PTC input)
Motor PTC
10 V = 100%
–
F
Through mode
Not Used
Select this setting when the terminal is not used or when using the terminal in the
pass-through mode.
–
10
Forward torque limit
Fwd Torque Limit
OLV
OLV
OLV
OLV
10 V = Motor rated torque
–
11
Reverse torque limit
Rev Torque Limit
OLV
OLV
OLV
OLV
10 V = Motor rated torque
–
12
Regenerative torque
limit
Regen Torq Limit
OLV
OLV
OLV
OLV
10 V = Motor rated torque
–
13
Torque reference/
Torque limit
Torque Reference
OLV
OLV
OLV
OLV
10 V = Motor rated torque
–
14
Torque compensation
Torque Comp
OLV
OLV
OLV
OLV
10 V = Motor rated torque
–
15
General torque limit
Torque Limit
OLV
OLV
OLV
OLV
10 V = Motor rated torque
–
16
Differential PID
feedback
PID Feedback 2
10 V = 100%
–
1F
Through mode
Not Used
Select this setting when the terminal is not used or when using the terminal in the
pass-through mode.
–
20
HAND Frequency
Reference
Hand Freq. Ref.
Full scale: Maximum frequency (E1-04)
–
22
Flow Meter
Flow Meter
Full scale: P6-01
–
23
Water Level or Suction
Input
WaterLvl/Suction
When Water Level Control is enabled (Q4-01 = 1):
0 V or 4 mA = 0 (ft)
10 V or 20 mA = Q4-02 (PSI) * 2.308 ft/PSI OR
When Suction Pressure Control is enabled (Q5-01 = 1)
0 V or 4 mA = 9 (PSI)
10 V or 20 mA = Q5-02 (PSI) OR
When Vacuum Control is enabled (Q5-01 = 2)
0 V or 4 mA = 0 (”Hg)
10 V or 20 mA = Q5-02 (”Hg)
–
24
PI Feedback Backup
PI FdBack Backup
Full scale: FB Device Scaling (P1-03)
–
27
PI Auxiliary Feedback
Level
PI Aux FB Level
0 V or 4 mA = 0 (unit based on Q6-22)
10 V or 20 mA = Q6-02 (unit based on Q6-22)
–
28
Differential PI Feedback Diff PI Feedback
Full scale: FB Device Scaling (P1-03)
–
pressure to be read in the drive.
pressure (or higher level of vacuum) to be read in the drive.
u
H4: Analog Outputs
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
H4-01
(041D)
Multi-Function Analog
Output Terminal FM
Monitor Selection
Term FM FuncSel
Selects the data to be output through multi-function analog
output terminal FM.
Set the desired monitor parameter to the digits available in
U
o
-
oo
.
For example, enter “103” for U1-03.
Default: 102
Range: 000 to
999
H4-02
(041E)
Multi-Function Analog
Output Terminal FM
Gain
Terminal FM Gain
Sets the signal level at terminal FM that is equal to 100% of the
selected monitor value.
Default: 100.0%
Min.: -999.9
Max.: 999.9
B.8 H Parameters: Multi-Function Terminals
310
YASKAWA TOEPYAIUPW01A YASKAWA AC Drive - U1000 iQpump Matrix Drive User Manual