B.9 L: Protection Function
L parameters provide protection to the drive and motor, including control during momentary power loss, stall prevention,
frequency detection, fault restarts, overtorque and undertorque detection, and other types of hardware protection.
u
L1: Motor Protection
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
L1-01
(0480)
Motor Overload
Protection Selection
Mtr OL Charact
0: OL1 Disabled
1: VT Motor
2: CT Motor
3: Vector Motor
6: 50Hz VT Motor
0: Disabled
1: General purpose motor (standard fan cooled)
2: Drive dedicated motor with a speed range of 1:10
3: Vector motor with a speed range of 1:100
6: General purpose motor (50 Hz)
The drive may not be able to provide protection when using
multiple motors, even if overload is enabled in L1-01. Set
L1-01 to 0 and install separate thermal relays to each motor.
Default:
Range: 0 to 3; 6
–
L1-02
(0481)
Motor Overload
Protection Time
MOL Time Const
Sets the motor thermal overload protection (oL1) time.
Default: 1.0 min
Min.: 0.1
Max.: 5.0
–
L1-03
(0482)
Motor Overheat Alarm
Operation Selection
(PTC input)
Mtr OH Alarm Sel
0 : Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm only
Sets operation when the motor temperature analog input
(H3-02, H3-10, or H3-06 = E) exceeds the oH3 alarm level.
0: Ramp to stop
1: Coast to stop
2: Fast Stop (decelerate to stop using the deceleration time in
C1-09)
3: Alarm only (“oH3” will flash)
Default: 3
Range: 0 to 3
–
L1-04
(0483)
Motor Overheat Fault
Operation Selection
(PTC input)
Mtr OH Fault Sel
0 : Ramp to Stop
1: Coast to Stop
2: Fast-Stop
Sets stopping method when the motor temperature analog input
(H3-02, H3-10, or H3-06 = E) exceeds the oH4 fault level.
0: Ramp to stop
1: Coast to stop
2: Fast Stop (decelerate to stop using the deceleration time in
C1-09)
Default: 1
Range: 0 to 2
–
L1-05
(0484)
Motor Temperature
Input Filter Time (PTC
input)
Mtr Temp Filter
Adjusts the filter for the motor temperature analog input
(H3-02, H3-10, or H3-06 = E).
Default: 0.20 s
Min.: 0.00
Max.: 10.00
–
L1-13
(046D)
Continuous
Electrothermal
Operation Selection
Mtr OL Mem Sel
0: Disabled
1: Enabled
2: Enabled(RTC)
0: Disabled
1: Enabled
2: Enabled (RTC)
Default: 1
Range: 0 to 2
–
<1> Default setting is determined by parameter A1-02, Control Method Selection.
u
L2: Momentary Power Loss Ride-Thru
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
L2-01
(0485)
Momentary Power Loss
Operation Selection
PwrL Selection
0: Disabled
1: Enbl with Timer
2: Enbl whl CPU act
0: Disabled. Drive trips on Uv1 fault when power is lost.
1: Recover within the time set in L2-02. Uv1 will be detected if
power loss is longer than L2-02.
2: Recover as long as CPU has power. Uv1 is not detected.
Default: 2
Range: 0 to 2
–
L2-02
(0486)
Momentary Power Loss
Ride-Thru Time
PwrL Ridethru t
Sets the Power Loss Ride-Thru time. Enabled only when L2-01
= 1 or 2.
Default: 0.5 s
Min.: 0.0
Max.: 2.5
–
L2-03
(0487)
Momentary Power Loss
Minimum Baseblock
Time
PwrL Baseblock t
Sets the minimum wait time for residual motor voltage decay
before the drive output reenergizes after performing Power Loss
Ride-Thru.
Increasing the time set to L2-03 may help if overcurrent or
overvoltage occur during Speed Search or during DC Injection
Braking.
Min.: 0.1 s
Max.: 5.0 s
–
L2-04
(0488)
Momentary Power Loss
Voltage Recovery Ramp
Time
PwrL V/F Ramp t
Sets the time for the output voltage to return to the preset V/f
pattern during Speed Search.
Min.: 0.0 s
Max.: 5.0 s
–