No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
P4-32
(0D19) Pre-Charge Level 2
PreCharge Level2
For normal PI operation during Pre-Charge 2, if the PI Feedback
signal rises above the P4-32 level, Pre-charge 2 is cancelled and
the drive resumes normal operation.
For inverse PI operation and during Pre-Charge 2, if the PI
Feedback signal goes below the P4-32 level, Pre-charge 2 is
cancelled and the drive resumes normal operation.
When set to zero, Pre-charge 2 still runs when P4-07 is set, but
uses P4-01 to determine if normal operation should resume.
Min.: 0.0
Max.: 6000.0
–
P4-36
(0D1D) Pressure Reached Exit
Conditions
Pressure Reached
0: Hyst Above
&Below
1: Hysteresis 1-Way
Determines Selects how the digital output reacts to Feedback
changes after it activates.
0: Hysteresis Above and Below
1: Hysteresis One Way
Default: 1
Range: 0, 1
–
P4-37
(0D1E) Pressure Reached
Hysteresis Level
Press Reach Hyst
Sets the hysteresis level for exiting the Pressure Reached
condition.
Min.: 0.1
Max.: 100.0
–
P4-38
(0D1F) Pressure Reached On-
Delay Time
PressReach OnDly
Sets the delay time that is applied prior to activating the Pressure
Reached condition.
Default: 1.0 s
Min.: 0.1
Max.: 60.0
–
P4-39
(0D20) Pressure Reached Off-
Delay Time
PressReachOffDly
Sets the delay time that is applied prior to deactivating the
Pressure Reached condition.
Default: 1.0 s
Min.: 0.1
Max.: 60.0
–
P4-40
(0D21) Pressure Reached
Detection Selection
PressReachDetSel
0: Always
1: Drive Running
2: Run Command
Sets the value that the drive status must match to trigger the
Pressure Detection digital output.
0: Always
1: Drive Running
2: Run Command
Default: 0
Range: 0 to 2
<1> Unit is determined by P1-02, System Units, setting.
<3> Unit text is set by P1-18, Prime Loss Detection Method.
u
P5: Pump HAND Mode
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
P5-01
(0D2C) HAND Mode Ref
Source
Hand Mode 1 Src
0: Analog Input
1: Hand Ref 1 (OPR)
Sets the HAND Mode reference.
0: Analog input
Note:
Analog input is defaulted to input A3 (0-10 V).
1: P5-02 (HAND reference)
Default: 1
Range: 0, 1
–
P5-02
(0D2D) HAND Reference 1
HAND Reference 1
Sets the frequency reference used when HAND Mode is active
and P5-01 is set to 1.
Default: 40.0 Hz
Min.: 0
Max.: [E1-04]
P5-03
(0D2E)
HAND/AUTO During
Run Selection
HAND/AUTO @Run
0: Disabled
1: Enabled
Selects whether the drive will permit switching between HAND
and AUTO Modes while running.
0: Disabled
1: Enabled
Default: 0
Range: 0, 1
–
P5-04
(0D2F)
HAND Key Function
Selection
Oper HAND Key
0: Disabled
1: Enabled
Enables and disables the HAND key on the HOA keypad.
0: Disabled
1: Enabled
Default: 1
Range: 0, 1
P5-05
(0D30) HAND Reference 2
HAND Reference 2
Sets the frequency reference used when HAND Mode 2 is
active.
Default: 0.0 Hz
Min.: 0.0
Max.: [E1-04]
–
P5-06
(0D31) HAND Ref. 1 Loss of
Prime Level
HandRef1 LOP Lvl
Detects loss of prime in the pump.
When the measured quantity determined by P1-18 drops below
this level for the time set in P1-20 and the output frequency is
at the level set in P5-02, a “Loss of Prime” condition occurs.
The drive responds to the “Loss of Prime” condition depending
on the setting of P1-22, Loss of Prime Selection.
Default: 0.0 A
Min.: 0.0
Max.: 1000.0
–
B.12 P: Pump Parameters
334