Register No.
Contents
002EH
Reserved
002FH
Frequency Reference Bias (from Up/Down 2 Function), 0.1% units
0030H
Reserved
0031H
Control Circuit Voltage, 1 Vdc units
0032H
Torque Reference (U1-09), 0.1% units
0033H
Reserved
0034H
Product Code 1 [ASCII], Product Type
0035H
Product Code 2 [ASCII], Region Code
0036H, 0037H
Reserved
0038H
PID Feedback, 0.1% units, unsigned, 100% / maximum output frequency
0039H
PID Input, 0.1% units, signed, 100% / maximum output frequency
003AH
PID Output, 0.1% units, signed, 100% / maximum output frequency
003BH, 003CH
Reserved
003DH
bit 0
CRC Error
bit 1
Data Length Error
bit 2
Reserved
bit 3
Parity Error
bit 4
Overrun Error
bit 5
Framing Error
bit 6
Timeout
bit 7 to bit F
Reserved
003EH
Output Frequency
r/min
003FH
0.01% units
0040H to 004AH
Used for various monitors U1-
oo
.
004BH
Drive status (U1-12)
bit 0
During Run
bit 1
During Zero Speed
bit 2
During Reverse Run
bit 3
During Fault Reset Signal Input
bit 4
During Speed Agree
bit 5
Drive Ready
bit 6
Alarm
bit 7
Fault
bit 8
During Operation Error (oPE
oo
)
bit 9
During Momentary Power Loss
bit A to B
Reserved
bit C
Auto Mode
bit D
Hand Mode
bit E
ComRef status, NetRef status
bit F
ComCtrl status
004CH to 007EH
Used for monitors U1-
oo
, U4-
oo
, U5-
oo
and U6-
oo
.
Refer to U2: Fault Trace on page 356
for parameter details.
007FH
Refer to Alarm Register Contents on page 403
for Alarm codes.
0080H to 0097H
Used for monitors U2-
oo
, U3-
oo
Refer to U: Monitors on page 353
for register value descriptions.
0098H, 0099H
U4-01 (Cumulative Operation Time)
Example: When U4-01 (Cumulative Operation Time) is 12345 hours, then 0098H = 1234 and 0099H = 5.
009AH, 009BH
U4-03 (Cooling Fan Operation Time)
Example: When U4-03 (Cooling Fan Operation Time) is 12345 hours, then 009AH = 1234 and 009BH = 5.
009CH to 00AAH
Reserved
C.9 MEMOBUS/Modbus Data Table