![YASKAWA U1000 iQpump Drive Скачать руководство пользователя страница 105](http://html2.mh-extra.com/html/yaskawa/u1000-iqpump-drive/u1000-iqpump-drive_user-manual_3308978105.webp)
n
Related Parameters
No.
Parameter Name
Setting Values
A1-01
Access Level Selection
Default: 2
Range: 0 to 3
A1-03
Initialize Parameters
Default: 0
Range: 0 to 5550; 6008 to 6014; 7770, 7771
E2-01
Motor Rated Current
Default:
Minimum: 10% of drive rated current
Maximum: 200% of drive rated current
E2-04
Number of Motor Poles
Default: 2
Minimum: 2
Maximum: 48
P1-03
Feedback Device Scaling
Default: 145.0 PSI
Minimum: 0.1
Maximum: 6000.0
P1-11
High Feedback Level
Default: 0.0 PSI
Minimum: 0.0
Maximum: 6000.0
P1-06
Minimum Pump Speed
Default: 40.0 Hz
Minimum: 0.0
Maximum: [E1-04]
P1-04
Start / Draw Down Level
Default: 0.0
Minimum: -999.9
Maximum: 999.9
P2-02
Sleep Level
Default: 0.0 Hz
Minimum: 0.0
Maximum: 6000.0
P4-10
AUTO Mode Operator Run Power Down Storage
Default: 0
Range: 0, 1
P5-02
HAND Speed Reference 1
Default: 40.0 Hz
Minimum: 0
Maximum: [E1-04]
P5-04
HAND Key Function Selection
Default: 1
Range: 0, 1
Q1-01
PID Controller Setpoint 1
Default: 0.0
Minimum: 0.0
Maximum: 6000.0
U1-99
Anti-No-Flow Timer
No signal output available
<1> Range is 0.0 to 999.9 with sign-bit “-” indicating Delta to Setpoint.
4.6 U1000 iQpump Presets and Functions
YASKAWA TOEPYAIUPW01A YASKAWA AC Drive - U1000 iQpump Matrix Drive User Manual
105
4
Start-Up Programming & Operation