No.
(Addr.
Hex)
Name
LCD Display
Description
Analog
Output Level
Unit
U6-07
(005F) q-Axis ACR Output
ACR(q) Output
OLV
OLV
OLV
OLV
Displays the output value for current control relative to motor
secondary current (q-Axis).
10 V: 200 Vrms
(-10 to +10 V)
0.1%
U6-08
(0060) d-Axis ACR Output
ACR(d) Output
OLV
OLV
OLV
OLV
Displays the output value for current control relative to motor
secondary current (d-Axis).
110 V: 200 Vrms
(-10 to +10 V)
0.1%
U6-80 to
U6-83
(07B0H
to 07B3)
Online IP Address
–
IP Address currently available; U6-80 is the most significant
octet.
No signal output
available
–
U6-84 to
U6-87
(07B4 to
07B7)
Online Subnet
–
Subnet currently available; U6-84 is the most significant octet.
No signal output
available
–
U6-88 to
U6-91
(07B8 to
07F1)
Online Gateway
–
Gateway currently available; U6-88 is the most significant octet.
No signal output
available
–
U6-92
(07F2) Online Speed
–
Link Speed
10: 10 Mbps
100: 100 Mbps
–
U6-93
(07F3) Online Duplex
–
Duplex Setting
0: Half
1: Full
–
U6-98
(07F8) First Fault
–
First Option Fault
–
–
U6-99
(07F9) Current Fault
–
Current Option Fault
–
–
<1> Values shown are specific to 200 V class drives. Double the values for 400 V class drives.
u
U9: Power Monitors
No.
(Addr.
Hex)
Name
LCD Display
Description
Analog
Output Level
Unit
U9-01
(0820) Electric Power (GWh)
GWh Consumed
Shows the total amount of electric power.
000 000 000 kW
U9-03
U9-02
U9-01
No signal output
available
1 GWh
U9-02
(0821) Electric Power (MWh)
MWh Consumed
No signal output
available
1 MWh
U9-03
(0822) Electric Power (kWh)
kWh Consumed
No signal output
available
1 kWh
U9-04
(0823)
Regenerative Power
(GWh)
GWh Produced
Shows the total amount of regenerated power.
000 000 000 kW
U9-06
U9-05
U9-04
No signal output
available
1 GWh
U9-05
(0824)
Regenerative Power
(MWh)
MWh Produced
No signal output
available
1 MWh
U9-06
(0825)
Regenerative Power
(kWh)
kWh Produced
No signal output
available
1 kWh
U9-07 to
U9-10
(0826 to
0829)
Electric Power Rates 1 to
4
Consumed
o
($)
These parameters show the electric power rate in Power Unit
Price (o4-19) that is calculated from the total electrical power
consumptions in U9-01 to U9-03.
U9-10: Digit 1 to digit 3
U9-09: Digit 4 to digit 6
U9-08: Digit 7 to digit 9
U9-07: Digit 10 to digit 12
000 000 000 000
U9-10
U9-09
U9-08
U9-07
The unit price is set in o4-19, and U9-07 to U9-10 are U9-01 to
U9-03 x o4-19.
No signal output
available
–
B.16 U: Monitors
362