B.13 Q: PID Controller Parameters
u
Q1: Preset Setpoint
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
Q1-01
(0E58) PID Controller Setpoint
1
Setpoint 1
Sets the PID Setpoint when b1-01 is set to 0.
Default: 0.0
Min.: 0.0
Max.: 6000.0
Q1-02
(0E59) PID Controller Setpoint
2
Setpoint 2
Sets the PID Setpoint when the “Multi Setpoint 1” or "Alternate
Multi Setpoint 1" multi-function digital input is closed.
Default: 0.0
Min.: 0.0
Max.: 6000.0
–
Q1-03
(0E5A) PID Controller Setpoint
3
Setpoint 3
Sets the PID Setpoint when the “Multi Setpoint 2” or "Alternate
Multi Setpoint 2" digital input is closed.
Default: 0.0
Min.: 0.0
Max.: 6000.0
–
Q1-04
(0E5B) PID Controller Setpoint
4
Setpoint 4
Sets the PID Setpoint when the “Multi Setpoint 1” and “Multi
Setpoint 2” or “Alternate Multi Setpoint 3” multi-function
digital inputs are closed.
Default: 0.0
Min.: 0.0
Max.: 6000.0
–
Q1-09
(0E60)
PID Setpoint Set via
Motor Operated Pot
Setpoint MOP
0: Disabled
1: Enabled
Selects whether parameters Q1-01 to Q1-04 are changed via
MOP from the home screen.
0: Disabled
1: Enabled
Default: 0
Range: 0, 1
–
<1> Unit text is set by P1-02, System Units. Scaling is set by P1-03, Feedback Device Scaling.
u
Q3: Output Current Limit
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
Q3-01
(0EBC)
Output Current Limit
Select
Current Lim Sel
0: Disabled
1: Enabled
Enables and disables the output current regulator.
0: Disabled
1: Enabled
Default: 0
Range: 0, 1
–
Q3-02
(0EBD) Current Limit
Current Limit
Sets the current limit. Value is internally limited to 300% of the
drive rated current.
Default: 0.0 A
Min.: 0.0
Max.: 1000.0
–
Q3-05
(0EC0)
Current Limit Regulator
Feedback Filter
Feedback Filter
First order filter time on the feedback used for Current Limit
control.
Default: 1000 ms
Min.: 5
Max.: 10000
–
Q3-06
(0EC1)
Current Limit Foldback
Message Style
Current Lim Msg
0: Full Screen Msg
1: Home Mon Text
Selects how the “Current Limit Foldback” message is displayed
on the operator.
0: Full Screen Message
1: Home Monitor Text
Default: 0
Range: 0, 1
u
Q4: Water Level Control
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
Q4-01
(0EEE) Water Level Selection
Water Level Sel
0: Disabled
1: Enabled
Enables and disables the water level control.
0: Disabled
1: Enabled
Default: 0
Range: 0, 1
–
Q4-02
(0EEF) Water Level Scaling
Water Lvl Scale
Sets the full scale (20 mA) output of the pressure transducer that
is connected to the analog input terminal programmed for
“WaterLvl/Suction” (H3-
oo
= 23).
Note:
1 PSI = 2.308 feet of water
Default: 100 PSI
Min.: 5
Max.: 500
–
B.13 Q: PID Controller Parameters
340
YASKAWA TOEPYAIUPW01A YASKAWA AC Drive - U1000 iQpump Matrix Drive User Manual